2-6
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
ETHERNET PORTS
CHAPTER 2: COMMUNICATION PORTS
Using the Quick Connect Feature via the USB Port
From the EnerVista 8 Series Setup software the
Quick Connect
button can be used to
establish a fast connection through the front panel USB port of an 869 relay.
Before starting, verify that the standard USB cable is properly connected from the laptop
computer to the front panel USB port.
1.
Verify that the latest version of the EnerVista 8 Series Setup software is installed
(available from the GE EnerVista CD or online from
http://www.gedigitalenergy.com/
multilin
). See the software installation section in the
869 Motor Management
System
instruction manual for installation details.
2.
Open the 8-Series Setup.
3.
Select the 869 device to start EnerVista 8 Series Setup.
4.
Click the
Quick Connect
button to open the Quick Connect dialog box.
5.
Set the
Interface
to USB, then click
Connect
.
6.
The EnerVista 8 Series Setup software creates a site named “Quick Connect” with a
corresponding device also named “Quick Connect” and displays them on the upper-
left corner of the screen. Expand the sections to view data directly from the
869 device.
Ethernet Ports
The following communication offerings are available.
Base Offering
Modes: 10/100 Mbps
One Port: RJ45
Protocol: Modbus TCP, TFTP
Communications Card Option
Modes: 100 MB
Two Ports: ST (with this option both enabled ports are on the communications card; the
Ethernet port located on the base CPU is disabled)
Protocols: Modbus TCP, DNP 3.0 TCP, IEC 60870-5-104, IEC 61850 MMS Server/GOOSE,
IEEE 1588, SNTP, IEC 62439-3 clause 4 (PRP), TFTP, SFTP
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...