CHAPTER 4: DNP 3
DNP IMPLEMENTATION
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
4-11
FASTPATH:
1.
A default variation refers to the variation response when variation 0 is requested and/
or in class 0, 1, 2, or 3 scans. The default variations for object types 1, 2, 20, 21, 22, 23,
30, and 32 are selected via relay settings. This optimizes the class 0 poll data size.
2.
For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a
request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests
sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for
changeevent objects, qualifiers 17 or 28 are always responded.)
Cold restarts are implemented the same as warm restarts – the 869 is not restarted, but
the DNP process is restarted.
2 (write)
00, 01 (start-stop)
07, 08 (limited quantity)
17, 28 (index)
---
---
50
1
Time and Date
(default - see Note 1)
1 (read)
2 (write)
00, 01 (start-stop)
06 (no range, or all)
07 (limited qty=1)
08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
52
2
Time Delay Fine
(quantity = 1)
129 (response)
07 (limited quantity)
---
---
60
0
Class 0, 1, 2, and 3
Data
1 (read)
20 (enable unsol)
21 (disable unsol)
22 (assign class)
06 (no range, or all)
---
---
1
Class 0 Data
1 (read)
22 (assign class)
06 (no range, or all)
---
---
2
Class 1 Data
1 (read)
20 (enable unsol)
06 (no range, or all)
07, 08 (limited quantity)
---
---
3
Class 2 Data
21 (disable unsol)
---
---
4
Class 3 Data
22 (assign class)
---
---
80
1
Internal Indications 1 (read)
00, 01 (start-stop)
(index =7)
129 (response)
00, 01 (start-stop)
2 (write)
(see Note 3)
00 (start-stop)
(index =7)
---
---
No Object (function
code only) see Note
3
13 (cold restart)
---
---
---
No Object (function
code only)
14 (warm restart) ---
---
---
No Object (function
code only)
23 (delay meas.)
---
---
---
OBJECT
REQUEST
RESPONSE
OBJECT
NO.
VARIATION
NO.
DESCRIPTION
FUNCTION
CODES (DEC)
QUALIFIER CODES (HEX) FUNCTION CODES
(DEC)
QUALIFIER CODES
(HEX)
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...