CHAPTER 4: DNP 3
DNP COMMUNICATION
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
4-3
The following setpoints are in the
PATH
:
SETPOINTS > DEVICE > COMMUNICATIONS > DNP
PROTOCOL
DNP CHANNEL 1 PORT
Range: NONE, NETWORK - TCP, NETWORK- UDP
Default: NONE
DNP CHANNEL 2 PORT
Range: NONE, NETWORK - TCP, NETWORK- UDP
Default: NONE
The DNP Channel 1 Port and DNP Channel 2 Port settings select the communications
port assigned to the DNP protocol for each channel. When this setting is set to “Network
- TCP,” the DNP protocol can be used over TCP/IP on channels 1 or 2. When this value is
set to “Network - UDP,” the DNP protocol can be used over UDP/IP.
FASTPATH:
If the additional communication module is not present, only RS485 is a possible option. The
Network options are hidden in this case and the DNP channel is assigned to the RS485 port
by default.
DNP ADDRESS
Range: 0 to 65519 in steps of 1
Default: 65519
Sets the DNP slave address. This number identifies this 869 on a DNP communications
link. Each DNP slave should be assigned a unique address.
DNP NETWORK CLIENT ADDRESS 1(2)
Range: Standard IP Address
Default: 0.0.0.0
The DNP Network Client Address settings can force the 869 to respond to a maximum of
two specific DNP masters.
DNP TCP/UDP PORT NUMBER 1 (2)
Range: 1 to 65535 in steps of 1
Default: 20000
The DNP NETWORK CLIENT ADDRESS 1(2) and DNP TCP/UDP PORT NUMBER 1(2) settings
are available only if the communications card is present. “DNP Channel 1 Port” takes the
“Port Number 1” and “Client Address 1” to allow or reject connections. The same relation
is used by channel 2.
23
Frozen Counter Value Change
since last read by client
30
User configured Analog Input
value
32
User configured Analog Input
value changed since last time
read by client
Analog Variation Numbers
Data Format
1
32-bit integer value with flag
2
16-bit integer value with flag
3
32-bit integer value without flag
4
16-bit integer value without flag
5
32-bit floating point value with flag
Object
DNP Data Type
869
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...