13-17-621 Page 186
Figure 215: Communication
6.7 Remote Control
The
Remote Control
diagnostics page is a diagnostics page which shows the current status of all available
remote control input signals. These parameters and their brief descriptions are listed below in Table 49.
Table 49: Remote Control
Remote Control
Signal Name
Brief Description
Remote Halt
If active machine will stop, mode can be immediate or timed for the
unload sequence
Remote Halt Enable
If assigned and active, remote halt input will function, If assigned and not
active, remote halt input will be ignored, If not assigned, remote halt
input will be treated as active.
Remote Load
If assigned and active, compressor loads immediately if discharge
pressure is below the unload pressure. If assigned and inactive,
compressor unloads immediately
Remote Load Enable
If assigned and active, remote load input is enabled, if assigned and not
active, remote load input is ignored.
Remote Timer Override
If assigned and active, the timer start functionality will be overridden so
that the machine will operate regardless of a start/stop timer schedule.
Secondary Pressure Activate
If active the secondary pressure band will be activated, if not active the
secondary pressure band is ignored.
Active Regulation
If active, normal pressure regulation is active, if assigned and not active,
compressor will begin unload sequence.
Active Regulation Enable
If assigned and active the active regulation input is followed, if assigned
and not active the active regulation input is ignored.
Active Capacity Limit
If assigned and active the capacity limits set on the HMI will be enabled,
if not active the limits will be ignored. When active, the speed of the
compressor motor will be limited.
Inlet Modulation Mode
If active, inlet modulation is forced to disabled and machine is run in
load/unload, if assigned and not active, inlet modulation is enabled
overriding the setting selected on the HMI.
Содержание Governor TEN014980
Страница 12: ...13 17 621 Page 12 Figure 4 Oblique View Figure 5 Rear View ...
Страница 165: ...13 17 621 Page 165 Figure 176 Sequencing Diagnostics ES Protocol Figure 177 Sequencing Diagnostics AirSmart Protocol ...
Страница 188: ...13 17 621 Page 188 Figure 217 VFD Diagnostics Figure 218 VFD Diagnostics ...
Страница 193: ...13 17 621 Page 193 Page left blank intentionally ...