13-17-621 Page 18
Input I/O Power Supply
Connection
designation
X07, X08, X09
X07, X08
X07, X08, X09
X07, X08
Input voltage
24 VDC -25%/+30%
Fuse
Required line fuse: Max. 10 A, slow-blow
Interfaces
Interface IF2
Conn designation
X02 RS485
Signal
RS485
Max. distance
1200 m
Transfer rate
Max. 115.2 kbit/s
Interface IF3
Conn designation
X03 RS485
-
X03 RS485
-
Signal
RS485
-
RS485
-
Max. distance
1200 m
-
1200 m
-
Transfer rate
Max. 115.2 kbit/s
-
Max. 115.2 kbit/s
-
Interface IF4
Conn designation
X0 CAN I/O
Signal
CAN bus
Max. distance
1000 m
Transfer rate
500.0 kbit/s
Digital Inputs
Quantity
8
Conn designation
X05, X06
Nominal voltage
24 VDC
Analog Inputs
Quantity
6
4
3
Conn designation
X11
Input
4 to 20 mA, 2-wire connections
Resistance measurement temperature inputs
Quantity
8X PT1000, 1X PTC
4X PT1000, 2X
PTC
2X PT1000, 2X
PTC
Conn designation
X12, X13
Input
Resistance measurement for 2-wire connections
Digital Output
Quantity
12
8
12
8
Conn Designation
X07, X08, X09
X07, X08
X07, X08, X09
X07, X08
Nominal Voltage
24 VDC
PWM Output
Quantity
1
Conn designation
X08
Nominal voltage
24 VDC -25%/+30%
Analog Output
Quantity
2
1
2
1
Conn designation
X10
Nominal voltage
4 to 20 mA with 2-wire connections
Power Supply
Conn designation
X01
Voltage range
24 VDC -5%/+30%
Power
consumption
7 W
6.5 W
5.6 W
4.3W
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation elevation above sea level
0 to 2000 m
No limitation
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
maximum
4500 m
Ambient Conditions
Содержание Governor TEN014980
Страница 12: ...13 17 621 Page 12 Figure 4 Oblique View Figure 5 Rear View ...
Страница 165: ...13 17 621 Page 165 Figure 176 Sequencing Diagnostics ES Protocol Figure 177 Sequencing Diagnostics AirSmart Protocol ...
Страница 188: ...13 17 621 Page 188 Figure 217 VFD Diagnostics Figure 218 VFD Diagnostics ...
Страница 193: ...13 17 621 Page 193 Page left blank intentionally ...