13-17-621 Page 136
C.142
Warning
Error during
updating serial
configuration on
Panel
An error occurred when
trying to update the serial
port configuration on the
controller. The operation
may have been
interrupted.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.143
Warning
Error in
sequencing
control task
An error occurred during
the operation of the
sequencing control task.
Internal software issue.
The operation may have
been interrupted.
Reboot the controller. If the problem persists,
export the logs from the controller and contact
Gardner Denver service.
C.144
Warning
Error in HMI
Serial
An error was detected in
serial communications
on the HMI serial port
(RS485-0).
Check wiring and all devices connected to the
RS485-0 port. Check configuration of the devices
to ensure that they match. This problem is
generally related to baud rate or other
communication misconfigurations. If the problem
persists, export the logs from the controller and
contact Gardner Denver service.
C.145
Warning
Error in IOBrick
RS485-1 Serial
An error was detected in
serial communications
on the IO Module serial
port RS485-1.
Check wiring and all devices connected to the
RS485-1 port. Check configuration of the devices
to ensure that they match. This problem is
generally related to baud rate or other
communication misconfigurations. If the problem
persists, export the logs from the controller and
contact Gardner Denver service.
C.146
Warning
Error in IOBrick
RS485-2 Serial
An error was detected in
serial communications
on the IO Module serial
port RS485-2.
Check wiring and all devices connected to the
RS485-2 port. Check configuration of the devices
to ensure that they match. This problem is
generally related to baud rate or other
communication misconfigurations. If the problem
persists, export the logs from the controller and
contact Gardner Denver service.
C.147
Warning
File Backup
Failure Warning
Backup operation failed.
The operation may have
been interrupted.
Attempt the backup operation again. If the
problem persists, export the logs from the
controller and contact Gardner Denver for
service.
C.148
Fault
Process Control
task entered an
unknown state.
An error was detected in
the process control task.
Internal software issue.
Export the logs from the controller and contact
Gardner Denver service.
C.149
Information
Archive
available
Informational. An archive
of logs is available for
download.
No action needed
C.150
Warning
Archiving
stopped
(maximum
number of
archives
reached)
Too many archive files
exist on the controller.
Export the logs from the controller. If the problem
persists, contact Gardner Denver service.
Fan Alarms
F1.0
Fault
Cooler Fan
Auxiliary Input
does not match
expected value
The contactor coil failed
or the wiring to the coil or
auxiliary contact is
disconnected. The
contactor could be stuck
in the open or closed
position.
Check wiring to the contactor coil and auxiliary
contact. Use the digital output IO diagnostics
function in the controller to check operation of the
contactor. If the contactor is not operating
properly use an ohm-meter to check the
resistance on the coil of the contactor. Attempt to
operate the contactor manually to ensure it is not
stuck in place.
Содержание Governor TEN014980
Страница 12: ...13 17 621 Page 12 Figure 4 Oblique View Figure 5 Rear View ...
Страница 165: ...13 17 621 Page 165 Figure 176 Sequencing Diagnostics ES Protocol Figure 177 Sequencing Diagnostics AirSmart Protocol ...
Страница 188: ...13 17 621 Page 188 Figure 217 VFD Diagnostics Figure 218 VFD Diagnostics ...
Страница 193: ...13 17 621 Page 193 Page left blank intentionally ...