13-17-621 Page 139
FV1.19
Fault
VFD Cooling
Power Board
EEPROM fault
VFD has detected
internal memory error.
Power cycle drive. Contact Gardner Denver
service.
FV1.20
Fault
VFD Cooling
RAM fault
VFD has detected
internal memory error.
Power cycle drive. Contact Gardner Denver
service.
FV1.21
Warning
VFD Cooling
Serial Flash
Warning
VFD has detected
internal memory error.
Power cycle drive. Contact Gardner Denver
service.
FV1.21
Fault
VFD Cooling
Serial Flash
Fault
VFD has detected
internal memory error.
Power cycle drive. Contact Gardner Denver
service.
FV1.25
Fault
VFD Cooling
MCU Watchdog
fault
VFD has detected
internal processing error.
Power cycle drive. Contact Gardner Denver
service.
FV1.32
Fault
VFD Cooling
Fan Cooling
fault
VFD has detected an
issue with its heat sink
cooling fans
Monitor the heat sink cooling fan operation. Using
a multi-meter check for 24VDC/48VDC at the
cooling fan pins during run (dependent on VFD
size). Replace cooling fans as needed.
FV1.36
Fault
VFD Cooling
Device
Compatibility
fault
VFD has detected and
compatibility error
between its control board
and power board.
Power cycle drive. Contact Gardner Denver
service.
FV1.37
Warning
VFD Cooling
Device Changed
warning
VFD has detected new
option card or control
board hardware
Power cycle drive. Contact Gardner Denver
service.
FV1.38
Warning
VFD Cooling
Device Added
warning
VFD has detected a new
option card has been
installed
Power cycle drive. Contact Gardner Denver
service.
FV1.39
Fault
VFD Cooling
Device
Removed fault
VFD has detected
removal of an Option
card
Power cycle drive. Contact Gardner Denver
service.
FV1.40
Fault
VFD Cooling
Unknown
Device fault
VFD has detected and
compatibility error
between its control board
and an option board.
Power down drive. Check option card and ribbon
cable are connected.
FV1.41
Fault
VFD Cooling
IGBT Temp fault
VFD has detected that
IGBT internal
temperatures are too
high, potentially caused
by high motor current
Check motor operating current at full load is not
exceeding nominal rating. Check wiring between
fan motor and VFD for incorrect or loose
connections. Verify supply voltage within
tolerance. Check fan wheel for proper alignment
and balance. If possible, manually spin fan wheel
and observe rotation. Test fan motor insulation
resistance.
FV1.51
Warning
VFD Cooling
External Input
Warning
VFD has detected
external fault input active
Check for any damage in external cable/wirings
and check if there is any loose connections or
terminal.
FV1.51
Fault
VFD Cooling
External Input
Fault
VFD has detected
external fault input active
Check for any damage in external cable/wirings
and check if there is any loose connections or
terminal.
FV1.55
Warning
VFD Cooling
Real Time Clock
warning
VFD reporting error with
the real time clock
Power cycle drive, Contact Gardner Denver
service
FV1.55
Fault
VFD Cooling
Real Time Clock
Fault
VFD reporting error with
the real time clock
Power cycle drive, Contact Gardner Denver
service
FV1.58
Fault
VFD Cooling
Current
Measure fault
VFD has detected an
error with its internal
current measuring
devices
Power cycle drive, Contact Gardner Denver
service
Содержание Governor TEN014980
Страница 12: ...13 17 621 Page 12 Figure 4 Oblique View Figure 5 Rear View ...
Страница 165: ...13 17 621 Page 165 Figure 176 Sequencing Diagnostics ES Protocol Figure 177 Sequencing Diagnostics AirSmart Protocol ...
Страница 188: ...13 17 621 Page 188 Figure 217 VFD Diagnostics Figure 218 VFD Diagnostics ...
Страница 193: ...13 17 621 Page 193 Page left blank intentionally ...