13-17-621 Page 166
Figure 178: Sequencing Diagnostics - Delcos Protocol - Master
Figure 179: Sequencing Diagnostics - Delcos Protocol - Slave
6.2 Jog Motors
The
Jog
Motor
diagnostics screen is used to run the motors in the system for a short amount of time to
make sure they are rotating in the right direction. Running the motor in the wrong direction can cause
damage to the machine. This function should be utilized anytime there is a risk that the AC power phases
changed sequence, such as on initial startup.
This page lists the following three parameters:
Jog Duration, Selected Motor,
and
Jog Delay
.
6.2.1 Jog Duration:
The Motor
Jog Duration
is the amount of time the motor will be run during the jog operation. The shortest
amount of time sufficient to turn the motor should be used. This value can be set between
0.2 Second, 0.5
Second,
and
1 second
. Figure 180 below shows the selection of
Jog Duration
set as
0.2 second
.
Содержание Governor TEN014980
Страница 12: ...13 17 621 Page 12 Figure 4 Oblique View Figure 5 Rear View ...
Страница 165: ...13 17 621 Page 165 Figure 176 Sequencing Diagnostics ES Protocol Figure 177 Sequencing Diagnostics AirSmart Protocol ...
Страница 188: ...13 17 621 Page 188 Figure 217 VFD Diagnostics Figure 218 VFD Diagnostics ...
Страница 193: ...13 17 621 Page 193 Page left blank intentionally ...