13-17-621 Page 63
4.2.7 Restart Delay Time
The
Restart Delay Time
sets the amount of time the controller will wait before restarting operation after a
power failure has occurred. The user can input the desired value on the number pad. Refer to Figure 81
below.
Figure 81: Restart Delay Time
4.2.8 p2 Timer Enable
The
p2 Timer Enable
setting allows the user to
enable
or
disable
the activation of the secondary pressure
band based on the timer control. The schedule for this timer is set under the
Timer Control
Settings
page.
When
p2 Timer Enable
is set to on the pressure set point will be automatically adjusted based on the
schedule. Refer to Figure 82 below.
Figure 82: p2 Timer Enable
4.2.9 Max Power Loss Time
The
Max Power Loss
defines the maximum duration of a power failure event that will still allow a restart of
the machine. Values can be set between 1 and 999 seconds. Refer to Figure 83 below for
Max Power
Loss
time entry screen. If the power failure occurs and continues for longer than the values set in the max
power loss time setting the controller will not allow the machine to restart and a power loss fault will be
registered.