13-17-621 Page 124
C.1
Fault
Machine
configuration
error
The machine
configuration file
selected is invalid,
corrupt, or otherwise not
compatible.
Check the machine definition and configuration
file selections and reload if necessary. If the
problem persists, export the logs from the
controller and contact Gardner Denver service.
C.2
Fault
Error on
Compressor
control task
Internal software error or
misconfiguration
Check the configuration settings. If the problem
persists, export the logs from the controller and
contact Gardner Denver service.
C.3
Warning
Date and Time
error
Error setting date and
time, most likely due to
invalid entries.
Check the date and time settings and attempt to
set them. If the problem persists, export the logs
from the controller and contact Gardner Denver
service.
C.4
Fault
Error in valve
control task
Internal software error or
misconfiguration
Check the configuration settings. If the problem
persists, export the logs from the controller and
contact Gardner Denver service.
C.5
Warning
Error on Data
log Task
Internal software or
hardware error
Export logs from the controller and contact
Gardner Denver service.
C.6
Fault
Error in Oil
control task
Internal software error or
misconfiguration
Check the machine configuration settings. If the
problem persists, export the logs from the
controller and contact Gardner Denver service.
C.7
Information
Manual
snapshot taken
Snapshot function
activated from machine
schematic view
None. Info captured with the snapshot event may
be viewed through the alarm history or by
exporting logs.
C.8
Warning
User access
task error
Internal software error or
misconfiguration
Export logs from the controller and contact
Gardner Denver service.
C.9
Warning
Error on FX30
USB link task
Internal error in
communication with
iConn module.
Check the iConn diagnostics page to verify
communication between the iConn and controller.
Check USB cable between the iConn and
controller and the power cable to the iConn. If the
problem persists, export the logs from the
controller and contact Gardner Denver service.
C.10
Warning
Error on alarm
info task
Internal software error or
corrupt alarm info file
detected.
Check functionality of the alarm info feature by
viewing the alarm info associated with alarms on
the system. If the problem persists, export the
logs from the controller and contact Gardner
Denver service.
C.11
Fault
Invalid
parameters in
Machine
Configuration
Invalid parameters were
detected in the machine
configuration file that
was attempted to be
loaded. This generally
indicates that the version
of the machine
configuration file does
not match the controller
firmware version.
Check the machine definition and configuration
file selections and reload if necessary. If the
problem persists, export the logs from the
controller and contact Gardner Denver service.
C.12
Warning
Error on Audit
page
Internal software error or
inability to save audit log
Check the functionality of the Audit log page. If
the problem persists, export the logs from the
controller and contact Gardner Denver service.
C.13
Fault
Error on cooling
control task
Internal software error or
misconfiguration
Check the machine configuration settings. If the
problem persists, export the logs from the
controller and contact Gardner Denver service.
C.14
Fault
Monitor Task
Error
Internal software error or
misconfiguration
Check the machine configuration settings. If the
problem persists, export the logs from the
controller and contact Gardner Denver service.
Содержание Governor TEN014980
Страница 12: ...13 17 621 Page 12 Figure 4 Oblique View Figure 5 Rear View ...
Страница 165: ...13 17 621 Page 165 Figure 176 Sequencing Diagnostics ES Protocol Figure 177 Sequencing Diagnostics AirSmart Protocol ...
Страница 188: ...13 17 621 Page 188 Figure 217 VFD Diagnostics Figure 218 VFD Diagnostics ...
Страница 193: ...13 17 621 Page 193 Page left blank intentionally ...