13-17-621 Page 151
within range at room temperature but still be
faulty once exposed to an elevated temperature
or vibration. Replace or repair the wiring or
sensor depending on the results of the findings.
P.143
Fault
Oil Injection
temperature
open fault
Oil Injection temperature
sensor is faulty, the
wiring to the sensor is
broken, or the wiring or
connector is
disconnected.
Using the wiring schematic for the machine,
locate the Oil Injection temperature sensor
connection to the controller. Check for
disconnected wires, plugs, or loose connections.
Inspect the cable for damage between the
controller and the sensor. Remove the cable
connector from the sensor and use a multi-meter
to check the resistance of the sensor and ensure
that it is not open (very high resistance). It is
possible that the sensor may read within range at
room temperature but still be faulty once exposed
to an elevated temperature or vibration. Replace
or repair the wiring or sensor depending on the
results of the findings.
P.159
Fault
Enclosure
temperature rate
fault
Enclosure temperature is
increasing at a rate
above the rate-of-rise
fault limit.
Check the site conditions and decrease the
ambient temperature in the compressor
enclosure.
P.160
Fault
Enclosure
temperature
high fault
Enclosure temperature
has exceeded the high
temp fault limit.
Check the site conditions and decrease the
ambient temperature in the compressor
enclosure.
P.160
Warning
Enclosure
temperature
high warning
Enclosure temperature is
approaching the high
temp fault limit.
Check the site conditions and decrease the
ambient temperature in the compressor
enclosure.
P.161
Fault
Enclosure
temperature low
fault
Enclosure temperature is
below the low temp fault
limit.
Check the site conditions and increase the
ambient temperature in the compressor
enclosure.
P.161
Warning
Enclosure
temperature low
warning
Enclosure temperature is
approaching the low
temp fault limit.
Check the site conditions and increase the
ambient temperature in the compressor
enclosure.
P.162
Fault
Enclosure
temperature
short fault
Enclosure temperature
sensor is faulty or the
wiring to the sensor is
shorted.
Using the wiring schematic for the machine,
locate the Enclosure temperature sensor
connection to the controller. Check for any
shorted wires at the connector. Inspect the cable
for damage between the controller and the
sensor. Remove the cable connector from the
sensor and use a multi-meter to check the
resistance of the sensor and ensure that it is not
shorted. It is possible that the sensor may read
within range at room temperature but still be
faulty once exposed to an elevated temperature
or vibration. Replace or repair the wiring or
sensor depending on the results of the findings.
Содержание Governor TEN014980
Страница 12: ...13 17 621 Page 12 Figure 4 Oblique View Figure 5 Rear View ...
Страница 165: ...13 17 621 Page 165 Figure 176 Sequencing Diagnostics ES Protocol Figure 177 Sequencing Diagnostics AirSmart Protocol ...
Страница 188: ...13 17 621 Page 188 Figure 217 VFD Diagnostics Figure 218 VFD Diagnostics ...
Страница 193: ...13 17 621 Page 193 Page left blank intentionally ...