13-9-666 Page 53
WARNING
It is mandatory that any water-cooled unit be installed in a shelter heated to
temperatures above freezing (32
°
F, 0
°
C).
Oil cooler malfunction may be traced by checking pressure at oil inlet and outlet. At normal operating air
service pressure (65 psig to 150 psig, 4.5 bar to 10.3 bar) with the unit warm, a pressure drop of 3 psi to
15 psi (.2 bar to 1 bar) can be expected between the oil inlet and the oil outlet.
Water pressure drop from water inlet to outlet will vary with the inlet pressure and amount of water
flowing. A normal pressure drop may range from 5 psi to 10 psi (.3 bar to .7 bar). Any change in the
pressure drop from that normally held may indicate tube leakage or fouling and should be investigated.
In many instances, the cooling water supply for the heat exchanger will contain impurities in solution
and/or suspension. These substances can cause scale formation, corrosion and plugging of any water-
cooled heat exchanger equipment. Disregarding the possibility that one or more of these conditions exist
may result in increased maintenance and operation expense, reduced equipment life and emergency
shutdown. It is strongly recommended that a reputable, local water treatment concern be engaged to
establish the corrosion, scale forming and fouling tendency of the cooling water and take steps necessary
to remedy the situation if a problem does exist. The need for water treatment may involve only filtration
(screening) to remove debris, sand and/or salt in the cooling water supply. However, chemical treatment
methods may be necessary in certain instances to inhibit corrosion and/or remove dissolved solids, to
alter the water’s tendency to form scale deposits, or prevent the growth of microorganisms. The normal
maintenance program for the unit should also include periodic cleaning of the tubes (water side) of the
heat exchanger to remove deposits which enhance fouling and corrosion.
Hex head zinc anodes are used in the return bonnet (opposite end to the water pipe connections) of heat
exchangers to provide internal water system corrosion protection. These anodes should be inspected
periodically and replaced when the zinc has been reduced to about 1/2 inch (13mm) in length.
Figure 5-10 – WATER CONTROL VALVE
Содержание ELECTRA-SAVER EAQ99Q
Страница 10: ...13 9 666 Page 3 Figure 1 4 COMPRESSOR MOTOR SIDE Figure 1 5 COOLER RESERVOIR SIDE 200EDM797 A Ref Drawing...
Страница 11: ...13 9 666 Page 4 Figure 1 6 AIR OIL FLOW DIAGRAM 202EDM797 Ref Drawing...
Страница 13: ...13 9 666 Page 6 DECALS 206EAQ077 212EAQ077 218EAQ077 211EAQ077 207EAQ077...
Страница 14: ...13 9 666 Page 7 DECALS 216EAQ077 217EAQ077 222EAQ077 221EAQ077 208EAQ077...
Страница 43: ...13 9 666 Page 36 Figure 4 13 WIRING DIAGRAM WYE DELTA EBQ EBU UNITS 300EDM546 A Ref Drawing...
Страница 44: ...13 9 666 Page 37 Figure 4 14 WIRING DIAGRAM FULL VOLTAGE EBQ EBU UNITS...
Страница 45: ...13 9 666 Page 38 Figure 4 15 WIRING DIAGRAM WYE DELTA EAQ EAU UNITS ONLY 301EAQ546 B Ref Drawing...
Страница 46: ...13 9 666 Page 39 Figure 4 16 WIRING DIAGRAM FULL VOLTAGE EAQ EAU UNITS ONLY 303EAQ546 Ref Drawing...
Страница 50: ...13 9 666 Page 43 Figure 5 3 FLOW DIAGRAM AIR OIL SYSTEM 203EDM797 A Ref Drawing...