13-9-666 Page 9
Air-Cooled Units
- A combination oil/aftercooler is supplied as standard equipment on all air-cooled
units. The air-cooled unit with the standard enclosure requires sufficient flow, Figure 2-2, for the
compressor oil/aftercooling system and for electric motor cooling. Air is drawn into the unit at the motor
side of the enclosure and is exhausted at the oil cooler side. Do not block the air flow to and from the
unit. Allow three and one-half (3-1/2) feet (1.1 m) to the nearest obstruction on the starter end and control
box end of the unit. Allow three (3) feet (.9 m) to the nearest obstruction above and on other sides of unit.
For continuous efficiency, oil cooler cores must be periodically cleaned with either vacuum or compressed
air. If wet cleaning is required, shield motor and spray on a mild soap solution and flush with clean water.
Minimum Air Flow * For Compression and Cooling
HP (kW)
Air Cooled
Water Cooled
125, 150, 200
(93, 112, 150)
17,000 cfm
481 m
3
/min
4,000 cfm
113 m
3
/min.
* 80
°
F (27
°
C) Inlet Air
Figure 2-2 – AIR FLOW CHART
WARNING
These compressors have aluminum oil coolers, do not use any cleaning
solution that is not compatible with aluminum. Use of improper solution may
result in damage to the cooler.
Water-Cooled Units
- The water-cooled unit with the standard enclosure requires sufficient air flow,
Figure 2-2, for electric motor cooling. Air is drawn into the unit at the top of the enclosure and is
exhausted at the motor side. Do not block air flow to and from unit. Allow three and one-half (3-1/2) feet
(1.1 m) to the nearest obstruction on the starter end and control box side of the unit. Allow three (3) feet
(.9 m) to the nearest obstruction above and on other sides of the unit.
FOUNDATION
- The Gardner Denver Rotary Screw compressor requires no special foundation, but
should be mounted on a smooth, solid surface. Whenever possible install the unit near level. Temporary
installation may be made at a maximum 10
°
angle lengthwise or 10
°
sidewise.
Mounting bolts are not normally required. However, installation conditions such as piping rigidity, angle of
tilt, or danger of shifting from outside vibration or moving vehicles may require the use of mounting bolts
and shims to provide uniform support for the base.
Содержание ELECTRA-SAVER EAQ99Q
Страница 10: ...13 9 666 Page 3 Figure 1 4 COMPRESSOR MOTOR SIDE Figure 1 5 COOLER RESERVOIR SIDE 200EDM797 A Ref Drawing...
Страница 11: ...13 9 666 Page 4 Figure 1 6 AIR OIL FLOW DIAGRAM 202EDM797 Ref Drawing...
Страница 13: ...13 9 666 Page 6 DECALS 206EAQ077 212EAQ077 218EAQ077 211EAQ077 207EAQ077...
Страница 14: ...13 9 666 Page 7 DECALS 216EAQ077 217EAQ077 222EAQ077 221EAQ077 208EAQ077...
Страница 43: ...13 9 666 Page 36 Figure 4 13 WIRING DIAGRAM WYE DELTA EBQ EBU UNITS 300EDM546 A Ref Drawing...
Страница 44: ...13 9 666 Page 37 Figure 4 14 WIRING DIAGRAM FULL VOLTAGE EBQ EBU UNITS...
Страница 45: ...13 9 666 Page 38 Figure 4 15 WIRING DIAGRAM WYE DELTA EAQ EAU UNITS ONLY 301EAQ546 B Ref Drawing...
Страница 46: ...13 9 666 Page 39 Figure 4 16 WIRING DIAGRAM FULL VOLTAGE EAQ EAU UNITS ONLY 303EAQ546 Ref Drawing...
Страница 50: ...13 9 666 Page 43 Figure 5 3 FLOW DIAGRAM AIR OIL SYSTEM 203EDM797 A Ref Drawing...