Servicing Motherboard Components
83
▼
Identify Faulty FB-DIMMs Using the
show
faulty
Command
The ILOM
show faulty
command displays current system faults, including faults
detected in FB-DIMMs.
●
Enter
show faulty
at the
->
prompt.
Related Information
■
“Identify Faulty FB-DIMMs Using the FB-DIMM Fault Locator Button” on page 83
▼
Identify Faulty FB-DIMMs Using the FB-DIMM
Fault Locator Button
Use the FB-DIMM Fault Locator button to identify faulty FB-DIMMs. This button is
located on the motherboard.
1. Extend the server to the maintenance position.
See
“Extend the Server to the Maintenance Position” on page 63
2. Disconnect power from the server.
See
“Removing Power From the System” on page 60
3. Remove the top cover.
See
“Remove the Top Cover” on page 67
4. Open the air duct to gain to access the FB-DIMM Fault Locator button.
5. Press the FB-DIMM Fault Locator button on the motherboard.
This will cause an amber LED associated with the faulty FB-DIMM to light for a
few minutes.
->
show faulty
Target | Property
| Value
--------------------+------------------------+-------------------------------
/SP/faultmgmt/0 | fru | /SYS/MB/CMP0/BR1/CH0/D0
/SP/faultmgmt/0 | timestamp | Dec 21 16:40:56
/SP/faultmgmt/0/ | timestamp | Dec 21 16:40:56 faults/0
/SP/faultmgmt/0/ | sp_detected_fault | /SYS/MB/CMP0/BR1/CH0/D0
faults/0 | | Forced fail(POST)
Содержание SPARC Enterprise T5140
Страница 1: ......
Страница 2: ......
Страница 6: ......
Страница 44: ...18 SPARC Enterprise T5140 and T5240 Servers Service Manual July 2009 FIGURE Diagnostics Flowchart ...
Страница 82: ...56 SPARC Enterprise T5140 and T5240 Servers Service Manual July 2009 ...
Страница 154: ...128 SPARC Enterprise T5140 and T5240 Servers Service Manual July 2009 ...
Страница 234: ...208 SPARC Enterprise T5140 and T5240 Servers Service Manual July 2009 ...
Страница 239: ......
Страница 240: ......