1-4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the Auto mode by remote controller, operation starts in the optimum
mode from among the Heating, Cooling, Dry and Monitoring mode.
During operation, the optimum mode is automatically switched in accordance with temperature changes.
The temperature can be set between 64°F (18°C) and 86°F (30°C) in 2°F (1°C) steps.
01-03
START
Room temp.
Ts + 4
°F(
2
°C)
?
COOLING (AUTO:DRY)
OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
AUTO CHANGEOVER operation flow chart
T
S
:
Setting temperature
Room temp.
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
Middle zone
NO
Operation mode
of outdoor unit : Cooling or Dry?
YES
NO
Operation mode
of outdoor unit : Heating?
YES
NO
YES
Outdoor temperature
77
°F(
25
°C)?
NO
YES
YES
NO
YES
YES
Ts - 4
°F(
2
°C)
?