03-29
Heater selection control by outdoor temperature 2
•
Temperature of heater on (Thon): Adjustable by function setting no. 62 (Operating temperature
switching of external heaters).
•
All control temperatures will shift by adjusting “Thon”.
•
Outdoor temperature zone boundary A and B: Adjustable by function setting no. 36 for outdoor
unit.
•
External heater output
•
Outdoor temperature zone
•
Operation status
NOTE:
In following operations, compressor will be on in heat pump prohibition zone.
•
Other than heating
•
Test run
Operation
Condition
Heater on
Heater is on as shown in following diagram of heating temperature.
Heater off
•
Heater is off as shown in following diagram of heating temperature.
•
Other than heating mode
•
Error occurred
•
Forced thermostat off
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-T
s ≥
0.9°F
(0.5°C)
Tr-Ts
Tr-Ts (=Thon
) ≤
-0.9°F
(
-0.5°C)
Combination zone
(Heat pump + Heater)
Heat pump prohibition zone
(Heater)
*A: -4°F (-20°C)
A + 3.6°F ( 2°C): -0.4°F (-18°C)
Outdoor temp.
*Adjustable by function setting no. 66.
On
On
12 V
Off
Off
0 V
Heater
Fan
Comp. On/Off
Outdoor temperature
(Factory setting)
Outdoor temperature zone *
Heat pump
prohibition
zone
Combination zone
* The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
46.4°F (8°C)
42.8°F (6°C)
-0.4°F (-18°C)
-4°F (-20°C)
Содержание AOU30RLXEH
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Страница 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Страница 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Страница 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...