1-2. HEATING OPERATION
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature,
and controls the operation frequency of the compressor.
If the room temperature is lower 9°F(4.5°C) than a set temperature,
the compressor operation frequency will attain to maximum frequency.
If the room temperature is higher 1°F(0.5°C) than a set temperature, the compressor will be stopped.
When the room temperature is b1°F(0.5°C) to -9°F(4.5°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table 2.
.
.
.
( Table 2 : Compressor frequency range )
Minimum
frequency
Maximum
frequency
AOU30RLXEH
18 rps
45 rps
Frequency
AOU30RLXEH
X zone
J zone
17 rps
15 rps
0 rps
Y zone
1-3. DRY OPERATION
The compressor rotation frequency shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Table 3.
Room temperature
Room temperature
Ts -1°F
(Ts -0.5°C)
Ts -3°F
(Ts -1.5°C)
( Fig.2 : Compressor control based on room temperature )
Ts : Setting temperature
X zone
Y zone
( Table 3 : Compressor frequency range )
Ts +3°F
(Ts +1.5°C)
(Ts +0.5°C)
Ts +1°F
J zone
01-02
Содержание AOU30RLXEH
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Страница 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Страница 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Страница 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...