In this mode, the "Operation Condition" and "Error Code" can be displayed by Push Switch on outdoor unit PCB
LED
Power / Mode
LED
Display Item
Compressor frequency
Upper fan speed (Outdoor unit)
Lower fan speed (Outdoor unit)
EEV pulse
Pressure sensor value (Low pressure range)
Pressure sensor value (High pressure range)
Outdoor air temperature sensor value
Discharge temperature sensor value
Heat-exchanger temperature sensor value (Middle)
Current value
Present Value
Of
Each Item
1
Compressor accumulated time
( Table 32 : Procedure for
present value )
Procedure
Operation
Power
Mode
Error L1 L2
L6
L5
L4
L3
1
2
3
4
During status display, press the MODE SWITCH 1 time.
(Status display : Outdoor unit is stopping and no error)
When the EXIT SWITCH is pressed, this mode ends
and returns to the status display.
Selecting display items can be done by pressing
the SELECT SWITCH. (Return to Procedure 3)
Press the ENTER SWITCH. (Data is displayed by lighting LED.
Refer to Table : 32)
When the POWER / MODE LED blinking 1 time,
press the ENTER SWITCH.
1
1
1
1
DATA
: Light ON
: Light OFF
: Blinking
1 :
1 Time Blinking
1-00. ERROR HISTORY MODE
1-33-2 Display mode
( Table 33 : Display pattern
)
: Light ON
: Light OFF
n :
n Time Blinking
5
1
Press the SELECT SWITCH and adjust to DISPLAY ITEM
(from L1 to L3) that you want to confirm. (Refer to Table : 32)
ERROR
L1
L2
L3
: Blinking
01-28
Содержание AOU30RLXEH
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Страница 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Страница 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Страница 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...