1-5. Setting the External input control
"Operation / Stop" mode or "Forced stop" mode can be selected.
( Factory setting)
Setting Description
Function Number
Setting Value
Operation / Stop mode 1
Operation / Stop mode 2
(Setting prohibited)
Forced stop mode
46
00
01
02
03
1-6. Setting the Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only,
change the setting to "Wired remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01)
When the setting value is set to “Both”(00),more suitable control of the room temperature
by setting function setting 30 and 31 too.
)
Setting Description
Function Number
Setting Value
Both
Wired remote controller
48
00
01
( Factory setting
03-02
1-4. Setting the Remote controller custom code (Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
( Factory setting)
Setting Description
Function Number
Setting Value
A
B
C
D
44
00
01
02
03
1-3. Setting the Room temperature sensor switching (Only for Wired remote controller)
When using the Wired remote controller temperature sensor , change the setting to “Both” (01).
( Factory setting)
Setting Description
Function Number
Setting Value
Indoor unit
Both
42
00
01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
Remote controller sensor must be turned on by using the remote controller.
Содержание AOU30RLXEH
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Страница 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Страница 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Страница 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...