SERVICE PARTS INFORMATION 4
Indoor unit fan motor
Test 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Test 2 : Check resistance of indoor fan motor
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Ground terminal)
>>If they are short-circuited (below 300 k ), replace Indoor fan motor and Controller PCB.
Pin number
(wire color)
Terminal function
(symbol)
1 (Red)
2
3
4 (Black)
5 (White)
6 (Yellow)
7 (Brown)
DC voltage (Vm)
No function
No function
Earth terminal (GND)
Control voltage (Vcc)
Speed command (Vsp)
Feed back (FG)
SERVICE PARTS INFORMATION 5
Test 1 : Check rotation of Fan
Outdoor unit fan motor
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Test 2 : Check resistance of Outdoor Fan Motor 1 or 2
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.
Pin number
(wire color)
Terminal function
(symbol)
1 (Red)
2
3 (Black)
4 (White)
5 (Yellow)
DC voltage (Vm)
No function
Earth terminal (GND)
Control voltage (Vcc)
Speed command (Vsp)
6 (Brown)
Feed back (FG)
02-49
Содержание AOU30RLXEH
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Страница 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Страница 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Страница 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...