1-7. Setting the Indoor unit fan control for energy saving for cooling
1-8 . Setting the Switching function for external output terminal
1-9 . Setting the Server room control switching
Enables or disables the power-saving function by controlling the indoor unit fan rotation
when the outdoor unit is stopped during cooling operation.
Functions of the external output terminal can be switched.
For details. refer to “External input and output”.
Switches between normal control and server room control.
To use this function, address setting of the primary unit and secondary unit needs to be done.
)
Setting Description
Function Number
Setting Value
Disable
49
00
Enable
01
Remote controller
02
( Factory setting
)
Setting Description
Function Number
Setting Value
Operation status
60
00
01-08
10
( Factory setting
)
Setting Description
Function Number
Setting Value
Nromal control
96
00
Server room control
(Primary unit)
01
02
( Factory setting
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02: Enable or disable this function by remote controller setting.
*When using a wired remote controller without Indoor unit fan control for energy saving for
cooling function, or when connecting a single split converter, the setting cannot be made
by using the remote controller. Set to “00” or “01”.
To confirm if the remote controller has this function, refer to the operating manual of each
remote controller.
(refer to Design & Technical
manual)
Other status
09
Error status
Indoor unit fan
operation status
Server room control
(Secondary unit)
Содержание AOU30RLXEH
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Страница 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Страница 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Страница 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...