03-14
NOTE:
Input of Operation/Stop depends on the setting of function setting 46.
00: Operation/Stop mode 1 (R.C. enabled)
01: (Setting prohibited)
02: Forced stop
03: Operation/Stop mode 2 (R.C. disabled)
Input signal type
•
Indoor unit
Input signal type is only "Edge".
•
External input and output PCB
The input signal type can be selected.
Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External input and
output PCB.
8
60-08
A
Cooling
thermostat On
Heating
thermostat On
Remote
controller output
External heater
output
9
60-09
B
Error status
Operation/Stop
Indoor unit fan
operation status
External heater
output
10
60-10
C
Indoor unit fan
operation status Operation/Stop
Error status
External heater
output
11
60-11
D
External heater
output
Operation/Stop
Indoor unit fan
operation status
Error status
12
60-12
D
Set point
attainment
status
Operation/Stop
Indoor unit fan
operation status
Error status
Mode
Function
setting
Rotary
SW
External output
Indoor unit
External input and output PCB
CN3
1
CN310
2
CN311
3
CN312
Edge
Edge
Pulse
The width of pulse must be longer than 200 msec.
Содержание AOU30RLXEH
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Страница 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Страница 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Страница 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...