1. External cause (Noise, temporary open, voltage drop) 2. Main PCB failure
Trouble shooting 14
OUTDOOR UNIT Error Method:
Outdoot Unit Main PCB Model
Information Error
Outdoor unit main PCB
Detective Actuators:
Detective details:
Indicate of Display:
Forecast of Cause:
Outdoor unit :
POWER
MODE
ERROR
2
6
(L1)
(L2)
(L6)
(L5)
(L4)
(L3)
2
PUMP
DOWN
LOW
NOISE
PEAK
CUT
02-17
Test 3 : Replace Controller PCB
Test 2 : Check Indoor unit electric components
YES
NO
Test 1-1 : Reset Power Supply and operate
Does Error indication show again?
Test 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and
Programmable Read Only Memory) is a non-
volatile memory which keeps memorized
information even if power is turned off. It can
change the contents electronically.
To change the contents, it uses higher
voltage than normal, and it can not change a
partial contents. (Rewriting shall be done
upon erasing the all contents.)
There is a limit in a number of rewriting.
Change Controller PCB.
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
1. When model information of EEPROM is incorrect.
2. When the access to EEPROM failed.
When power is on and there is some below case.
Indoor Unit :
Operation lamp: 6 times Flash,
Timer lamp : 2 times Flash
ERROR CODE : [E : 62]
n: n times blinking
: Light ON
: Light OFF
Содержание AOU30RLXEH
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 36: ...R410A WALL MOUNTED type INVERTER 2 TROUBLE SHOOTING ...
Страница 89: ...R410A WALL MOUNTED type INVERTER 3 APPENDING DATA ...
Страница 96: ...3 1 3 Procedures to change the Function Setting 03 07 ...
Страница 120: ...3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jun 2016 Printed in Japan ...