03-27
Heat pump prohibition control
•
Temperature of heater on (Thon): Adjustable by function setting no. 62 (Operating temperature
switching of external heaters).
•
All control temperatures will shift by adjusting “Thon”.
Operation status
NOTE:
In following operations, compressor will be on.
•
Other than heating
•
Test run
Operation
Condition
Heater on
Heater is on as shown in following diagram of heating temperature.
Heater off
•
Heater is off as shown in following diagram of heating temperature.
•
Other than heating mode
•
Error occurred
•
Forced thermostat off
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-T
s ≥
0.9°F
(0.5°C)
Tr-Ts
Tr-Ts (=Thon
) ≤
-0.9°F
(
-0.5°C)
On
0.9°F (0.5°C)
-0.9°F (-0.5°C)
On
12 V
On
Off
Off
0 V
Off
Heating operation
Heater
Fan
Air conditioner
Room temperature
Set temp.
3 min or more