Attention
Troubleshooting 34
Forecast of cause:
Check Point 2 : Check outdoor unit operation
Check Point 1 : Check indoor unit
Check Point 3 : Check site condition
Check Point 5 : Check refrigeration cycle
Check Point 4 :
Check indoor / outdoor installation condition
Pipe (In)
Pipe (Out)
Pipe (In)
Pipe (Out)
OK
OK
OK
OK
OK
OK
OK
OK
MPa MPa
No Cooling / No Heating (unworking)
1. Indoor unit error
2. Outdoor unit error
3. Effect by surrounding environment
4. Connection pipe / connection wire failure
5. Refrigeration cycle failure
Does indoor unit FAN run on HIGH FAN?
Is air filter dirty?
Is heat-exchanger clogged?
Check if energy-save function is operated.
Check if outdoor unit is operating
Check any objects that obstruct the air flow route.
Check clogged heat-exchanger.
Is the valve open?
Is capacity of indoor unit fitted to room size?
Any windows open? Or direct sunlight ?
Check connection pipe
(specified pipe length & Pipe diameter?)
Check any loose or removed communication line.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data & Technical
Manual.
Check if strainer is clogged (Refer to the figure at right).
Measure Gas Pressure and if there is a leakage, correct it.
>> When recharging the refrigerant, make sure to perform
vacuuming, and recharge the specified amount.
Check EEV (Parts information 3)
Check Compressor (Parts information 1, 2)
Strainer normally does not have temperature difference
between inlet and outlet as shown in , but if there is a
difference like shown in , there is a possibility of inside
clogged. In this case, replace Strainer.
03-46
Содержание AMUG24LMAS
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Страница 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Страница 105: ......
Страница 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Страница 146: ......
Страница 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...