5. COOLING OPERATION
A sensor (room temperature thermistor) built in an indoor unit body usually perceives
difference or variation between set temperatu re and present room temperature,
and controls operation frequency of the compressor.
* When the room temperature is 7°F(3.5°C) higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
04-06
* When the room temperature is b7°F(+3.5°C) to -1°F(-0.5°C) of the setting temperature,
the compressor frequency is controlled within the range shown in Table 1.
* When the room temperature is 1°F(0.5°C) lower than a set temperature, the compressor will be stopped.
6. DRY OPERATION
Compressor frequency is defined by the set temperature
and room temperature as below.
Ts + 1°F
(Ts + 0.5°C)
Ts - 1°F
(Ts - 0.5°C)
Ts - 3°F
(Ts - 1.5°C)
Ts + 3°F
(Ts + 1.5°C)
Operating frequency
X zone J zone Y zone
29 rps
29 rps
0 rps
39 rps
39 rps
0 rps
76 rps
76 rps
0 rps
AOU24RGLX
AOU30RGLX
AOUG36LMAS1
76 rps
76 rps
0 rps
AOUG48LMAS1
Room
Room
temperature
temperature
X zone
J zone
Y zone
Содержание AMUG24LMAS
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Страница 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Страница 105: ......
Страница 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Страница 146: ......
Страница 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...