![Fujitsu AMUG24LMAS Скачать руководство пользователя страница 79](http://html.mh-extra.com/html/fujitsu/amug24lmas/amug24lmas_service-manual_118226079.webp)
Troubleshooting 23-2
Detective details:
Forecast of cause:
1. Connector connection failure
2. Pressure sensor failure
3. Main PCB failure
Detective actuators:
Outdoor unit main PCB
03-31
Outdoor unit discharge pressure sensor error
(AOUG36/48LMAS1)
Indicate or Display:
Indoor unit
Operation lamp: 8 times Flash,
Timer lamp : 6 times Flash
Wired remote control
Error code : [E : 86]
n: n times blinking
: Light ON
: Light OFF
Mode Error
2
8
6
Outdoor unit (AOUG36/48LMAS1)
30 seconds or more after power-on,
when pressure sensor detection value
detects the condition below continuosly
for 30 seconds or more.
Ps
≤
43.51 psi (0.30 Mpa)
or Ps
≥
725.19 psi (5.00 Mpa)
・
Check if the terminal connection is loose.
・
Check if connector is removed.
・
Check if cable is open.
・
Check if connector is erroneous connection.
Test 2 : Check voltage from main PCB (Parts information 8)
Test 1 : Check the connection of the pressure sensor
DC
DC
With the connector connected to the PCB,
measure the voltage between CN92:2-3
of the main PCB.
Characteristics of pressure sensor
4.5
(5.0)
0.5
0
Output [DCV]
Pressure [psi (MPa)]
362.59
725.19
PRESSURE
SENSOR
PS
(2.5)
2.5
>> Upon correcting the removed connector or miss-wiring, reset the power.
OK
If the voltage is not on the connector, replace Main PCB.
If the voltage is incorrect value, replace the Pressure sensor.
1
2
3
1
RED
WHITE
BLACK
2
3
CN92
+
-
A
B
C
D
E
F
Содержание AMUG24LMAS
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Страница 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Страница 105: ......
Страница 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Страница 146: ......
Страница 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...