Troubleshooting 25
Compressor motor control error
(Stoppage permanently)
03-33
Detective actuators:
Detective details:
Forecast of cause:
Outdoor unit main PCB
Compressor
Transistor PCB
1. Defective connection of electric components
2. Main PCB failure
3. Compressor failure
4. Transistor PCB (IPM) failure
While running compressor, if the detected rotor location is out of
phase with actual rotor location more than 90° (36/48 models 105 ),
the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
Indicate or Display:
Indoor unit
Operation lamp: 9 times Flash,
Timer lamp : 5 times Flash
Wired remote control
Error code : [E : 95]
n: n times blinking
: Light ON
: Light OFF
Mode Error
2
9
5
Outdoor unit (AOUG36/48LMAS1)
A
B
C
D
E
F
°