12. OFF DEFROST OPERATION CONTROL
1. OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation
lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost,
and then stop.
In heating operation, the outdoor heat-exchanger temperature is less than 24.8
°
F (
-4°C)
, and
compressor operation integrating time lasts for more than 30 minutes.
3. OFF DEFROST FLOWCHART
Heating operation stop
Outdoor heat exchanger temp. :
Below 24.8
°F
(
-4°C)
and
Compressor integrating operation :
Over 30 minutes
Defrost start
Defrost Indicator: [Operation lamp]
7 sec ON / 2 sec OFF (AOUG36,48LMAS1)
Outdoor heat-exchanger temperature : Over 55.4
°F
(
13°C)
(AOU24, 30RGLX)
59.0
°F
(
15°C)
(AOUG36, 48LMAS1)
or
Compressor ON time : Maximum 15 minutes
Defrost end
2. OFF DEFROST RELEASE CONDITION
Outdoor heat-exchanger temperature is higher than 55.4
°F
(
13°C)
(AOU24, 30RGLX)
59.0
°F
(
15°C)
(AOUG36, 48LMAS1)
or
Compressor operation time has passed 15 minutes.
OFF defrost operation is released when the conditions becomes as below.
04-28
6 sec ON / 2 sec OFF (AOU24,30RGLX)
Содержание AMUG24LMAS
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Страница 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Страница 105: ......
Страница 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Страница 146: ......
Страница 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...