03-35
Troubleshooting 26
Detective actuators:
Detective details:
Forecast of cause:
Outdoor unit fan motor 1 error
Outdoor unit main PCB
Outdoor unit fan motor
1. Fan rotation failure
2. Motor protection by surrounding temperature rise
3. Main PCB failure
4. Outdoor unit fan motor failure
When outdoor fan rotation speed is less than 100rpm in 20 seconds
after fan motor starts, fan motor stops.
After fan motor restarts, if the same operation within 60sec is
repeated 3 times in a row, compressor and fan motor stops.
If and repeats 5 times in a row, compressor
and fan motor stops permanently.
Indicate or Display:
Indoor unit
Operation lamp: 9 times Flash,
Timer lamp : 7 times Flash
Wired remote control
Error code : [E : 97]
n: n times blinking
: Light ON
: Light OFF
Mode Error
2
9
A
B
F
E
D
C
7
Outdoor unit (AOUG36/48LMAS1)