Auxiliary equipment control by room temperature
Auxiliary equipment control is switchable by room temperature. Auxiliary equipment switching is per-
formed for each room temperature divided to following 3 zones.
Tr
Ts +0.9°F (0.5 °C)
Ts -0.9°F (0.5 °C)
Ts
Zone C
Zone A
Zone B
Ts: Setting temperature
Tr: Room temperature
Zone
Application
When temperature dropping
When temperature rising
Primary
Auxiliary
Primary
Auxiliary
A
Both of primary and auxiliary equipment
is unnecessary.
Off
Off
Off
Off
B
Primary heater only.When room
temperature stays in zone B for a long
time, auxiliary equipment also operates.
On
Off*
1
—
—
C
Auxiliary equipment also operates.
On
On*
2
On
On*
2
*1: For standby time for auxiliary equipment operation, refer to indoor unit function number 71
*2: When indoor unit function number 61 is set to "00", auxiliary equipment operates according to the
following conditions.
• Ts - Tr > 21.6 °F (-12.0 °C): Auxiliary equipment turn off.
• Ts - Tr > 18.0 °F (-10.0 °C): Auxiliary equipment turn on.
4-4. Details of function
- (05-36) -
4. External input and output
FIELD
WORKING
FIELD
WORKING
Содержание AMUG24LMAS
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Страница 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Страница 105: ......
Страница 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Страница 146: ......
Страница 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...