Operation status
*: The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
Combination zone
Heat pump only zone
On
12 V
Off
0 V
Heater
Comp. On/Off
Outdoor temperature
(Factory setting)
Outdoor temperature zone *
46.4°F (8°C)
42.8°F (6°C)
-0.4°F (-18°C)
-4°F (-20°C)
On
Off
On
Off
Fan
DIP-SW101-3 On
DIP-SW101-3 Off
NOTE:
In following operations, compressor will be on in heat pump prohibition zone.
• Other than heating
• Test run
4-4. Details of function
- (05-44) -
4. External input and output
FIELD
WORKING
FIELD
WORKING