Auxiliary heater control by outdoor temperature 2
This control selects heat pump or external heater according to the outdoor temperature. Even when
outdoor temperature is high, the heating is performed by using both of heat pump and external
heater.
Operation
Condition
Heater on
Heater is on as shown in following diagram of heating temperature.
Heater off
DIP-SW101-3
On
•
Heater is off as shown in following diagram of heating
temperature.
•
Other than heating mode
•
Error occurred
•
Forced thermostat off
•
Fan stop protection
Indoor unit fan
setting for
external heater
Enabled
DIP-SW101-3
Off
•
Heater is off as shown in following diagram of heating
temperature.
•
Other than heating mode
•
Error occurred
•
Forced thermostat off
Indoor unit fan
setting for
external heater
Disabled
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
• Outdoor temperature zone boundary A: Adjustable by function setting number 66.
•
External heater output
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Tr-Ts
Off
On
*
Tr-Ts ≥ 0.9°F
(0.5°C)
Tr-Ts (=Thon) < -0.9°F (-0.5°C)
*: When room temperature stays in this zone for a specific time, auxiliary heater is turned on. For
details, refer to function number 71.
•
Outdoor temperature zone
Combination zone
(Heat pump + Heater)
Heat pump prohibition zone
(Heater)
A: -4°F (-20°C)*
A + 3.6°F ( 2°C): -0.4°F (-18°C)
Outdoor temp.
*: Adjustable by function setting 66
4-4. Details of function
- (05-41) -
4. External input and output
FIELD
WORKING
FIELD
WORKING
Содержание AMUG24LMAS
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Страница 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Страница 105: ......
Страница 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Страница 146: ......
Страница 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...