Discharge temperature sensor error
AOU24RGLX
AOU30RGLX
OK
OK
DC
CN63
THERMISTOR (DIS.TEMP.)
BROWN
BROWN
1
3
2
1
3
2
AOUG36LMAS1
AOUG48LMAS1
CN63
THERMISTOR (COMP SHELL)
THERMISTOR (DIS.TEMP.)
BL
AC
K
BL
AC
K
B
LA
C
K
B
LA
C
K
1 2
3 4
1 2
3 4
Discharge temperature thermistor short detected
Discharge thermistor open detected
1. Connector connection failure, open
2. Thermistor failure
3. Main PCB failure
Check Point 1 : Check connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check thermistor
Thermistor characteristics check (Disconnect thermistor from PCB and check.)
Check Point 3 : Check voltage of main PCB (DC 5.0V)
Main PCB (CN63:1-3) voltage value = 5V (AOU24/30RGLX)
Main PCB (CN63:1-2) voltage value = 5V (AOUG36/48LMAS1)
Disconnect thermistor from main PCB, and check voltage.
If the voltage does not appear, replace main PCB,
and execute the check operation again.
03-25
Troubleshooting 18
Detective details:
Discharge temperature thermistor
Detective actuators:
Forecast of cause :
Indicate or Display:
Indoor unit
Operation lamp: 7 times Flash,
Timer lamp : 1 time Flash
Wired remote control
Error code : [E : 71]
n: n times blinking
: Light ON
: Light OFF
Mode Error
2
7
1
Outdoor unit (AOUG36/48LMAS1)
(PARTS INFORMATION 7)
A
B
F
E
D
C
Содержание AMUG24LMAS
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Страница 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Страница 105: ......
Страница 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Страница 146: ......
Страница 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...