![Fujitsu AMUG24LMAS Скачать руководство пользователя страница 199](http://html.mh-extra.com/html/fujitsu/amug24lmas/amug24lmas_service-manual_118226199.webp)
•
Outdoor temperature zone
Heater only zone
Combination zone
(Heat pump + Heater)
Heater only zone
B: 42.8°F (6°C)*
A: -4°F (-20°C)*
B + 3.6°F (2°C): 46.4°F (8°C)
A + 3.6°F (2°C): -0.4°F (-18°C)
Outdoor temp.
*: Adjustable by function setting 66 and 67
•
Operation status
On
12 V
Off
0 V
Heater
Comp. On/Off
Outdoor temperature
(Factory setting)
Outdoor temperature zone *
* The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
46.4°F (8°C)
42.8°F (6°C)
-0.4°F (-18°C)
-4°F (-20°C)
Combination zone
Heat pump prohibition zone
On
Off
On
Off
Fan
DIP-SW101-3 On
DIP-SW101-3 Off
NOTE:
In following operations, compressor will be on in heat pump prohibition zone.
• Other than heating
• Test run
4-4. Details of function
- (05-51) -
4. External input and output
FIELD
WORKING
FIELD
WORKING
Содержание AMUG24LMAS
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 07 15 SR_CH01_AR024EF_01 ...
Страница 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 07 15 SR_CH02_AR024EF_01 ...
Страница 47: ...3 TROUBLESHOOTING 2020 07 15 SR_CH03_AR024EF_01 ...
Страница 105: ......
Страница 106: ...4 CONTROL AND FUNCTIONS 2020 07 15 SR_CH04_AR024EF_01 ...
Страница 146: ......
Страница 147: ...5 FILED WORKING 2020 07 15 SR_CH05_AR024EF_01 ...