2-19
Chapter 2
3. Function Explanation
2
When function code “H18 Torque control” is set to be active
(value 1 or 2), this operation can be canceled externally.
Assign value
“23”
to the target digital input terminal and
switch between active and inactive in this input signal state.
Frequency and operation commands from the link can be
enabled or disabled by switching the external digital input
signal. Select the command source in “H30 Serial link”.
Assign value
“24”
to the target digital input terminal and
switch between valid or invalid in this input signal state.
Assigning value
“25”
to a digital input terminal renders the
terminal a universal DI terminal. The ON/OFF state of signal
input to this terminal can be checked through the RS-485 or
optional BUS.
This input terminal is only used to check for an incoming input
signal through communication and does not affect inverter
operation.
The start mode (rotating motor pick-up) in function code H09
can be enabled or disabled by switching the external digital
input signal. Assign value
“26”
to the target digital input
terminal and enable or disable the function in this input signal
state.
Torque control cancel [Hz/TRQ]
: 23
Set value
input signal
Function selected
23
Torque control function active
off
The input voltage to terminal 12 is the torque com-
mand value.
Torque control function inactive
on
The input voltage to terminal 12 is the frequency
command value.
PID feedback amount when PID control operation is
selected (H20 = 1 or 2).
H18
Link enable (RS-485: standard, Bus: option) [LE]
: 24
Set value
input signal
Function selected
24
off
Link command invalid.
on
Link command valid
Pick up start mode [STM]
: 26
Universal DI [U-DI]
: 25
These functions are used for PG-Option or SY-Option card.
Refor to each instruction manual.
Set value
input signal
Function selected
26
off
Start mode disabled.
on
Start mode enabled.
H30
H09
SY-PG enable (Option) [PG/Hz]
: 27
Zero speed command with PG option [ZERO]
: 29
Synchronization command (Option) [SYC]
: 28
Pre-exciting command with PG option [EXITE]
: 32
Forced stop command with Deceleration
[STOP1]
: 30
Forced stop command with Deceleration
time 4 [STOP2]
:31
Normally this terminal should be “ON”, when this terminal
goes off durring motor running, the motor decelerates to stop,
and outputs alarm “Er6”.
In case of terminal [STOP2], the decelertion time is deter-
mined by E15 (DEC TIME4).
This function is prioritized under any operation (Terminal,
Keypad, Communication...operation).
Settings when shipped from the factory
Digital input
Setting at factory shipment
Set value
Description
Terminal X1
0
Multistep freq. selection [SS1]
Terminal X2
1
Multistep freq. selection [SS2]
Terminal X3
2
Multistep freq. selection [SS4]
Terminal X4
3
Multistep freq. selection [SS8]
Terminal X5
4
ACC/DEC selection [RT1]
Terminal X6
5
ACC/DEC selection [RT2]
Terminal X7
6
3-wire operation stop command [HLD]
Terminal X8
7
Coast-to-stop command [BX]
Terminal X9
8
Alarm reset [RST]
ON
ON
Er6
ON
ON
FWD or REV
[STOP1] or
[STOP2]
Alarm
In case of [STOP2],
time is fixed by E15
(DEC TIME4)
Output
frequency
Chapter02J(P6˜25).p65
07.8.9, 12:26
Page 19
Adobe PageMaker 6.5J/PPC
Содержание FRENIC5000G11S Series
Страница 1: ......
Страница 2: ......
Страница 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Страница 166: ...4 12...
Страница 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Страница 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Страница 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Страница 235: ......
Страница 236: ......