1-5
Chapter 1
1. Standard Specifications
1
1.4 Three-phase 460V FRENIC5000P11S Series
(for variable torque load)
Item
Specifications
Type
FRN
■■■
■■■
P11S-4UX
007 010 015 020 025 030 040 050 060 075 100 125 150 200 250 300 350 400 450 500 600 700 800
Nominal applied motor
HP
7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600 700 800
Rated capacity *1)
kVA
10 13 18 24 29 35 48 60 72 89 119 140 167 201 242 300 330 386 414 517 589 668 764
Rated voltage *2)
V
3-phase 380, 400, 415V/50Hz 380, 400, 440, 460V/60Hz
Output
Rated current *3)
A
12.5 16.5 23 30 37 44 60 75 91 112 150 176 210 253 304 377 415 520 585 650 740 840 960
raitings
Overload capability
110% of rated current for 1min
Rated frequency
Hz
50, 60Hz
Phases, Voltage, Frequency
3-phase 380 to 480V 50/60Hz 3-phase 380 to 440V/50Hz 380 to 480V/60Hz *4)
Voltage / frequency variations
Voltage : +10 to –15% (Voltage unbalance *5) : 2% or less) Frequency :+5 to –5%
Momentary voltage dip capability
When the input voltage is 310V or more, the inverter can be operated continuously.
Input
*6)
When the input voltage drops below 310V from rated voltage, the inverter can be operated for 15ms .
ratings
The smooth recovery method is selectable.
Rated current
*7) (with DCR)
10.0 13.5 19.8 26.8 33.2 39.3 54 67 81 100 134 160 196 232 282 352 385 491 552 624 704 792 880
A (without DCR)
21.5 27.9 39.1 50.3 59.9 69.3 86 104 124 150 -
-
-
-
-
-
-
-
-
-
-
-
-
Required power supply
capacity *8)
kVA
7.0 9.4 14 19 24 28 38 47 57 70 93 111 136 161 196 244 267 341 383 433 488 549 610
Maximum frequency
50 to 120Hz
Setting
Base frequency
25 to 120Hz
Starting frequency
0.1 to 60Hz, Holding time: 0.0 to 10.0s
Carrier frequency *9)
0.75 to 15kHz
0.75 to 10kHz
0.75 to 6kHz
Output
Accuracy (Stability)
· Analog setting :
±
0.2% of Maximum frequency (at 25
±
10
°
C (77
±
50
°
F))
frequency
· Digital setting :
±
0.01% of Maximum frequency (at –10 to +50
°
C (14 to 122
°
F))
Setting resolution
· Analog setting : 1/3000 of Maximum frequency ex.) 0.02Hz at 60Hz, 0.04Hz at 120Hz
· Digital setting :
0.01Hz at Maximum frequency of up to 99.99Hz (0.1Hz at Maximum frequency of 100Hz and above)
· LINK setting
: Selects from the following two items.
• 1/20000 of Maximum frequency ex.) 0.003Hz at 60Hz, 0.006Hz at 120Hz
• 0.01Hz (Fixed)
Voltage / freq. (V/f) characteristic
Adjustable at base and maximum frequency, with AVR control : 320 to 480V
Torque boost
Torque boost can be set, using Function code F09 and A05.
0.0
: Automatic (for constant torque load)
Control
0.1 to 0.9 : Manual (for variable torque load) *10)
1.0 to 1.9 : Manual (for propotional speed torque load)
2.0 to 20.0 : Manual (for constant torque load)
Starting torque
50%
Braking torque
*11)
20%
10 to 15%
Standard Time
s
No limit
Duty cycle
%ED
No limit
Standard Braking torque
100%
75%
Using
Time
s
15
7
8
10
Braking
Duty cycle
%ED
3.5
3.5
4
10
options 10%ED Braking torque
100%
*13)
Time
s
15
7
Duty cycle
%ED
10
10
7
DC injection braking
Starting frequency: 0.1 to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 100% of rated current
* Inverter restarts at the starting frequency when operation command is input while braking is operating.
* DC injection braking does not operate at the time of change-over from forward to reverse operation.
* DC injection braking does not operate when frequency setting is decreased while operation command (FWD, REV) is being input.
Enclosure (IEC 60529)
IP 40
IP 00 ( IP 20 : Option )
Cooling method
Fan cooling
-UL/cUL
-Low Voltage Directive
-EMC Directive
-TÜV (up to 30HP)
Standards
-IEC 61800-2 (Ratings, specifications for low voltage adjustable frequency a.c. power drive systems)
-IEC 61800-3 (EMC product standard including specific test methods)
Weight
lbs
13 13 13 22 22 23 64 64 75 86 88 106 154 154 221 221 309 309 309 551 551 794 794
(kg)
(6.1) (6.1) (6.1) (10) (10) (10.5) (29) (29) (34) (39) (40)
(70) (70) (100) (100) (140) (140) (140) (250) (250) (360) (360)
NOTES: *1)
Inverter output capacity (kVA) at 460V. Rated capacity reduces when power supply voltage decreases.
*2)
Output voltage cannot exceed the power supply voltage.
*3)
Current derating may be required in case of low impedance loads such as high frequency motor.
*4)
When the input voltage is 380 to 398V/50Hz or 380 to 430V/60Hz, the tap of the auxiliary transformer must be changed.
*5)
Use a DC REACTOR (DCR) when the voltage unbalance exceeds 2%. (This value is equivalent to FUJI’s conventional allowable value.)
Voltage unbalance (%) = Max. voltage [V] – Min. Voltage [V] x 67
(Conforming to EN61800-3 (5.2.3))
Three-phase average voltage[V]
*6)
Tested at standard load condition (85% load).
*7)
This value is under FUJI original calculation method.
*8)
When power-factor correcting DC REACTOR (DCR) is used.
*9)
When inverter is operating at a carrier frequency of 10kHz or higher, the inverter may automatically reduce the carrier frequency to 8kHz for protecting inverter.
*10) When torque boost is set at 0.1, starting torque of 50% or more can be obtained.
*11) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.)
*12) Consult with Fuji Electric.
*13) Applicable to 10%ED when using options (standard)
(48)
Chapter01J(P1˜5).p65
07.8.9, 11:53
Page 5
Adobe PageMaker 6.5J/PPC
Содержание FRENIC5000G11S Series
Страница 1: ......
Страница 2: ......
Страница 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Страница 166: ...4 12...
Страница 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Страница 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Страница 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Страница 235: ......
Страница 236: ......