1-16
Chapter 1
2. Common Specifications
High Performance Functions
Function
Setting range
Unit
Min.
Factory setting
Remarks
Code Name
LCD monitor
unit
30HP
40HP
H03
Data initializing
H03
DATA INIT
0 : Manual set value
(Data reset)
1 : Return to factory set value
H04
Auto-reset
(Times)
H04
AUTO-RESET
0 (Inactive), 1 to 10 times
H05
(Reset interval)
H05
RESET INT
2 to 20s
H06
Fan stop operation
H06
FAN STOP
0
: Inactive
1
: Active (Fan stops at low temperature mode (2HP
or larger)
H07
ACC/DEC
(Mode select)
H07
ACC PTN
0
: Linear
pattern
1
: S-curve (weak)
2
: S-curve (strong)
4
: Non-linear (For variable torque load)
H08
Rev. phase sequence lock
H08
REV LOCK
0
: Inactive
1 : Active
H09
Start mode
H09
START MODE
0
: Inactive
(Rotating motor pick up)
1
: Active (Only Auto-restart after momentary power failure mode )
2
: Active (All start mode)
H10
Energy-saving operation
H10
ENERGY SAV
0
: Inactive
1
: Active (Only when torque boost "F09" is in
manual setting mode
H11
DEC mode
H11
DEC MODE
0
: Normal (According to "H07" mode)
1
: Coast-to-stop
H12
Instantaneous
H12
INST CL
0
: Inactive
overcurrent limiting
1
: Active
H13
Auto-restart (Restart time)
H13
RESTART t
0.1 to 10.0s
H14
(Freq. fall rate)
H14
FALL RATE
0.00 to 100.00 Hz/s
H15
(Holding DC voltage)
H15
HOLD V
200 to 300V (230V)
400 to 600V (460V)
H16
(OPR command selfhold time)
H16
SELFHOLD t
0.0 to 30.0s, 999s (999s: The operation command is
held during DC link circuit voltage is larger than 50V)
H18
Torque control
H18
TRQ CTRL
G11S 0 : Inactive (Frequency control)
1 :
Active (Torque control by terminal 12 (Driving))
(0 to +10V/0 to 200%)
2 :
Active (Torque control by terminal 12 (Driving &
Braking))
(0 to +10V/0 to 200%)
P11S 0 : Inactive (Fixed)
H19
Active drive
H19
AUT RED
0
: Inactive
1
: Active
H20
PID control (Mode select)
H20
PID MODE
0
: Inactive
1
: Active
2
: Active (inverse operation mode)
H21
(Feedback signal)
H21
FB SIGNAL
0
: Terminal 12 (0 to +10V)
1
: Terminal C1 (4 to 20mA)
2
: Terminal 12 (+10 to 0V)
3
: Terminal C1 (20 to 4mA)
H22
(P-gain)
H22
P-GAIN
0.01 to 10.00
H23
(I-gain)
H23
I-GAIN
0.0 : Inactive
0.1 to 3600.0s
H24
(D-gain)
H24
D-GAIN
0.00 : Inactive
0.01 to 10.0s
H25
(Feedback filter)
H25
FB FILTER
0.0 to 60.0s
H26
PTC thermistor (Mode select)
H26
PTC MODE
0
: Inactive
1
: Active
H27
(Level)
H27
PTC LEVEL
0.00 to 5.00V
H28
Droop operation
H28
DROOP
G11S: -9.9 to 0.0Hz
P11S : 0.0 (Fixed)
H30
Serial link(Function select)
H30
LINK FUNC
(Code) (Monitor)
(Frequency
(Operation
command)
command)
0 :
X
-
-
1:
X
X
-
2 :
X
-
X
3 :
X
X
X
(X: Valid -: Invalid)
H31
RS-485
(Address)
H31
485ADDRESS
1 to 31
H32
(Mode select on no
H32
MODE ON ER
0
: Trip and alarm (Er8)
response error)
1
: Operation for H33 timer, and alarm (Er8)
2
:
Operation for H33 timer,and retry to communicate.
* If the retry fails, then the inverter trips("Er 8").
3
: Continuous operation
H33
(Timer)
H33
TIMER
0.0 to 60.0s
H34
(Baud rate)
H34
BAUD RATE
0
: 19200 bit/s
1
: 9600
2
: 4800
3
: 2400
4
: 1200
When data code is set at "1", all
function data is returned to
initial data (factory setting data).
Automatically returns to "0"
after initializing.
Time required until motor residual
voltage reduces to zero.
P11S series does not have
this function.
Gain for frequency setting
is disabled.
When the acceleration time is
longer than 60s, this function
prevents inverter trip due to
overvurrent, to accelerates
motor in a shortest time.
E01-E09:20
C33
E01-E09:21
P11S does not have this
function.
Selects type of LINK
operation in LINK operation
mode.
F01:11, C30:11,
E01-E09:24,25, F02
-
-
0
-
1
0
s
1
5
-
-
0
-
-
0
-
-
0
-
-
0
-
-
G11S:0
P11S:1
-
-
0
-
-
1
s
0.1
0.5
Hz/s
0.01
10.00
V
1
230V class : 235V
460V class : 470V
s
0.1
999
-
-
0
-
-
0
-
-
0
-
-
0
-
-
1
-
0.01
0.1
s
0.1
0.0
s
0.01
0.00
s
0.1
0.5
-
-
0
V
0.01
1.60
Hz
0.1
0.0
-
-
0
-
1
1
-
-
0
s
0.1
2.0
-
-
1
The function marked can be set while the inverter is running. Other functions must be set while the inverter is
stopped.
Chapter01J(P6˜18).p65
07.8.9, 11:53
Page 16
Adobe PageMaker 6.5J/PPC
Содержание FRENIC5000G11S Series
Страница 1: ......
Страница 2: ......
Страница 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Страница 166: ...4 12...
Страница 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Страница 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Страница 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Страница 235: ......
Страница 236: ......