![FujiFilm FRENIC5000G11S Series Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/fujifilm/frenic5000g11s-series/frenic5000g11s-series_technical-information_2343268056.webp)
2-8
Chapter 2
3. Function Explanation
■
F03 Maximum frequency 1
This function sets the maximum output frequency for motor 1.
- Setting range G11S: 50 to 400Hz
P11S: 50 to 120Hz
Setting a value higher than the rated value of the equipment to
be driven may damage the motor or machine. Match this
value with the rating of the equipment.
■
F04 Base frequency 1
This function sets the maximum output frequency in the
constant-torque range of motor 1 or the output frequency at
the rated output voltage. Match this value with he rating of the
motor.
- Setting range G11S: 25 to 400Hz
P11S: 25 to 120Hz
NOTE:
When the set value of base frequency 1 is higher than that of
maximum output frequency 1, the output voltage does not increase to
the rated voltage because the maximum frequency limits the output
frequency.
■
F05 Rated voltage 1
This function sets the rated value of the voltage output to
motor 1. Note that a voltage higher than the supply (input)
voltage cannot be output.
- Setting range 230V: 0, 80 to 240V
460V: 0, 320 to 480V
Value 0 terminates operation of the voltage regulation function,
thereby resulting in the output of a voltage proportional to the
supply voltage.
NOTE:
When the set value of rated voltage 1 exceeds maximum output
voltage 1, the output voltage does not increase to the rated voltage
because the maximum output voltage limits the output voltage.
■
F06 Maximum voltage 1
This function sets the maximum value of the voltage output for
motor 1. Note that a voltage higher than the supply (input)
voltage cannot be output.
- Setting range 230V: 80 to 240V
460V: 320 to 480V
F03
MAX Hz-1
■
F07 Acceleration time 1
■
F08 Deceleration time 1
This function sets the acceleration time for the output fre-
quency from startup to maximum frequency and the decelera-
tion time from maximum frequency to operation stop.
- Setting range Acceleration time 1: 0.01 to 3600s
Deceleration time 1: 0.01 to 3600s
Acceleration and deceleration times are represented by the
three most significant digits, thereby the setting of three high-
order digits can be set.
Set acceleration and deceleration times with respect to
maximum frequency. The relationship between the set
frequency value and acceleration/deceleration times is as
follows:
Set frequency = maximum frequency
The actual operation time matches the set value.
Set frequency < maximum frequency
The actual operation time differs from the set value.
Acceleration/deceleration operation time
= set value x (set frequency/maximum frequency)
NOTE:
If the set acceleration and deceleration times are too short even
though the resistance torque and moment of inertia of the load are
great, the torque limiting function or stall prevention function is
activated, thereby prolonging the operation time beyond that stated
above.
F05
RATED V-1
F04
BASE Hz-1
F07
ACC TIME1
F06
MAX V-1
F08
DEC TIME1
0
Output voltage
Constant-torque range
F06 Maximum
voltage 1
F05 Rated
voltage 1
Output
frequency
F04 Base
frequency 1
F03 Maximum
frequency
Start
Stop
Output
frequency
Maximum frequency
Set frequency
Acceleration time
Deceleration time
Time
Output
frequency
Acceleration
operation time
Deceleration
operation time
Acceleration time
Deceleration time
Maximum frequency
Set frequency
Time
Stop
Start
Chapter02J(P6˜25).p65
07.8.9, 12:26
Page 8
Adobe PageMaker 6.5J/PPC
Содержание FRENIC5000G11S Series
Страница 1: ......
Страница 2: ......
Страница 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Страница 166: ...4 12...
Страница 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Страница 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Страница 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Страница 235: ......
Страница 236: ......