![FujiFilm FRENIC5000G11S Series Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/fujifilm/frenic5000g11s-series/frenic5000g11s-series_technical-information_2343268054.webp)
2-6
Chapter 2
3. Function Explanation
■
F00 Data protection
Setting can be made so that a set value cannot be changed by
KEYPAD panel operation.
- Set value 0: The data can be changed.
1: The data cannot be changed.
[Setting procedure]
0
→
1 : Press the
STOP
and
keys simultaneously to
change the value from 0 to 1, then press the
FUNC
DATA
key to validate the change.
1
→
0 : Press the
STOP
and
keys simultaneously to
change the value from 1 to 0, then press the
FUNC
DATA
key to validate the change.
■
F01 Frequency command 1
This function selects the frequency setting method.
E01 to E09
0: Setting by KEYPAD panel operation (
,
key).
1: Setting by voltage input (terminal 12) (0 to +10Vdc, 0 to
5Vdc).
2: Setting by current input (terminal C1) (4 to 20mAdc).
3: Setting by voltage input + current input (terminal 12 +
terminal C1) (0 to +10V + 4 to 20mA).
The setting frequency is determined by adding inputs to
terminals 12 and C1.
4: Reversible operation with polarized voltage input (terminal
12). (-10 to +10Vdc)
5: Reversible operation with polarized voltage input (terminal
12) + voltage command auxiliary input (optional terminal
V1) (-10 to +10Vdc)
The setting frequency is determined by adding inputs to
terminals 12 and V1.
* Polarized input allows operation in the direction opposite
that of an operation command.
6: Inverse mode operation (terminal 12) (+10 to 0Vdc)
7: Inverse mode operation (terminal C1) (20 to 4mA)
8: Setting by UP/DOWN control mode 1 (initial value = 0)
(terminals UP and DOWN)
E01 to E09
9: Setting by UP/DOWN control mode 2 (initial value = last
final value) (terminals UP and DOWN)
See the function explanation of E01 to E09 for details.
10: Setting by PATTERN operation
C21 to C28
11: Setting by DI option or Pulse train input (Option)
For details, see the instruction manual on options.
F00
DATA PRTC
3. Function Explanation
3.1 Fundamental Functions
F01
FREQ CMD1
•
Forward and inverse operation
■
F02 Operation method
This function sets the operation command input method.
- Set value 0: KEYPAD operation (
FWD
,
REV
, and
STOP
keys).
Input from terminals FWD and REV is ignored.
1: Operation by external input (terminals FWD
and REV).
• This function can only be changed when terminals FWD and
REV are open.
• REMOTE/LOCAL switching from the KEYPAD panel
automatically changes the set value of this function.
F02
OPR METHOD
0
0
4
20 mA
-10
0
+10V
Frequency setting value
Frequency setting value
Forward operation
(set value: 1, 3, 4, 5)
Maximum frequency
- Maximum frequency
Maximum frequency
(set value: 1, 3)
Inverse operation
(set value: 6)
V1: Option
Analog input terminal (12), (V1)
Analog input terminal (C1)
(set value: 4, 5 )
Forward operation
(set value: 2, 3)
Inverse operation
(set value: 7)
• “ ” means the related functions and the set value
Chapter02J(P6˜25).p65
07.8.9, 12:26
Page 6
Adobe PageMaker 6.5J/PPC
Содержание FRENIC5000G11S Series
Страница 1: ......
Страница 2: ......
Страница 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Страница 166: ...4 12...
Страница 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Страница 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Страница 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Страница 235: ......
Страница 236: ......