![FujiFilm FRENIC5000G11S Series Скачать руководство пользователя страница 116](http://html1.mh-extra.com/html/fujifilm/frenic5000g11s-series/frenic5000g11s-series_technical-information_2343268116.webp)
2-68
Chapter 2
4. Standard RS-485 Interface
Data format [11]
Capacity code
Example) If 30kW
Since 30 x 100 = 3000 = 0BB8
H
0 B B 8
Data format [12]
Exponential data (ACC/DEC time, current
value, display coefficient)
Example) If "F07:Acceleration time 1" = 20.0s,
20.0 = 0.1 x 200
⇒
0400
H
+ 00C8
H
= 04C8
H
0 4 C 8
Data format [13]
Pattern operation
Data format [14]
Operation command
Example) If "S06:Operation command" = FWD, X1, X5 = ON
0000 0000 0100 0101
b
= 0045
H
0 0 4 5
Data format [15]
Y1-Y5 output terminal
Example) If "M15:Y1-Y5 output terminal" = Y1, Y5 = ON
0000 0000 0001 0001
b
.= 0011
H
0 0 1 1
Data format [16]
Operating status
Code
Capacity (kW)
Code
Capacity (kW)
5
0.05
10
0.1
20
0.2
40
0.4
75
0.75
150
1.5
220
2.2
370
3.7
550
5.5
750
7.5
1100
11
1500
15
1850
18.5
2200
22
3000
30
3700
37
4500
45
5500
55
7500
75
9000
90
11000
110
13200
132
16000
160
20000
200
22000
220
25000
250
28000
280
31500
315
35500
355
40000
400
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0
Data portion
Index
portion
Polarity
Not used
0 : 0.01
X
001
〜
999
(0.00
〜
9.99)
1 : 0.1
X
100
〜
999
(10.0
〜
99.9)
2
:
1
X
100
〜
999
(100
〜
999)
3
:
10
X
100
〜
999
(1000
〜
9990)
0 : Positive (+), 1 : Negative (-)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0
Data portion
Index
portion
Rotating direction
Not
used
Time
0 : 0.01 X
000
〜
999
(0.00
〜
9.99)
1 : 0.1
X
100
〜
999
(10.0
〜
99.9)
2 : 1
X
100
〜
999
(100
〜
999)
3 : 10
X
100
〜
999
(1000
〜
9990)
0 : Forward rotation, 1: Reverse rotation
0 : ACC/DEC time 1
1 : ACC/DEC time 2
2 : ACC/DEC time 3
3 : ACC/DEC time 4
Example) If "C22:Stage1" = 10.0s R2 (10s, reverse
rotation, acceleration time 2/deceleration time 2),
10.0 = 0.1 x 100
⇒
9000
H
+ 0400
H
+ 0064
H
= 9464
H
9 4 6 4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
0 0 0 0 X9 X8 X7 X6 X5 X4 X3 X2 X1
REV
RST
FWD
0
Not used
Multifunction input FWD:
Forward rotation command
REV :
Reverse rotation command
(All bits are ON by 1)
Alarm reset
command
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
0 0 0 0 0 0 0 0 0 0 0 Y5 Y4 Y3 Y2 Y1
0
Not used
Output terminal
(All bits are ON by 1)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
BUSY
RL
ALM
DEC
ACC
IL
VL
TL
NUV
BRK
INT
EXT
REV
FWD
(All bits are ON or active by 1)
WR
FWD: In forward operation
REV: In reverse operation
EXT: In DC braking (or in pre-excitation)
INT:
Inverter trip
BRK: In braking
NUV: DC link voltage establishment (undervoltage at 0)
TL:
In torque limiting
VL:
In voltage limiting
IL:
In current limiting
ACC: In acceleration
DEC: In deceleration
ALM: Alarm
RL:
Transmission valid
WR: Function writing right
0: Keypad panel
1: RS-485
2: Link (option)
BUSY: In data writing (processing)
Example) Monitoring method is similar as in the formats
[14] and [15].
Chapter02J(P44˜74).p65
07.8.9, 12:26
Page 68
Adobe PageMaker 6.5J/PPC
Содержание FRENIC5000G11S Series
Страница 1: ......
Страница 2: ......
Страница 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Страница 166: ...4 12...
Страница 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Страница 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Страница 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Страница 235: ......
Страница 236: ......