Chapter 6
2. FRENIC5000G11S/P11S Series
6-24
Caution
The information described in this catalog is for the purpose of selecting the appropriate products.
Before actually using this product, be sure to read the instruction manual carefully to ensure proper
operation.
1. PID control functions built in as standard
• By controlling the cold/warm water temperature of the air
handling unit uniformly, the energy savings can be realized in
accordance with the reduced amount of pump flow that
accommodates changes in the room temperature.
• Till recently, a temperature controller has been required.
However, because PID control functions are built in as
inverter functions, the water temperature can be controlled
uniformly simply by installing a temperature sensor (4 to
20mA) at the pump outlet.
2. Greater energy saving effect obtainable combined
with automatic energy saving operation function
• Normally, the cold/warm water pump has the variable torque
characteristics. The axial force of the pump is directly
proportional to the rotating speed cubed. If the rotating
speed (amount of flow) drops to 80%, the axial force will be
approximately 50%. As a result, compared with the amount
of flow when the flow is restricted by the valve, significant
energy savings can be expected.
• Moreover, you can anticipate greater energy savings by
setting the automatic energy-saving operation function
(Function code: H10) to 1 (Active).
3. Unnecessary to resort to any special sound-
proofing measures; Fuji inverter drives a motor
with silent motor sound.
• We have succeeded in eliminating most of the unpleasant
motor sound that usually comes from the motor which is
driven by the inverter.
The sound levels are comparable to those of commercial
power sources.
■
Wiring diagram/System configuration
2.11 Using with Cold/Warm Water Pumps
■
Advantages
Sensor power
supply unit
4 to 20mA
current output (*)
(
+
)
(
-
)
Control power supply
Temperature sensor
Cold/warm water pump
Heat exchanger
Alarm output
(for any fault)
"Inverter running"
signal output
Output for inverter panel
cooling fan operation command
Heat storage unit
Air chiller
Cold water pump
Ice storage tank
Heat exchanger
Brine pump
L1/R
L2/S
L3/T
13
12
11
C1
FWD
CM
X1(Hz/Hz1)
CM
FAB (MCCB)
Device for setting
the cold/warm water temp.
0 to 1k
Ω
From sensor current
output (*)(4 to 20mA)
Relay for operation command
FX
Relay for PID control cancel
Hz/PID
P1
P(+)
N(-)
U
V
W
30C
30B
30A
30
Y5C
Y5A
Y1
CME
G
DC REACTOR
(DCR)
Keypad panel
FRN G11S-
FRN P11S-
VR
(
+
)
(
-
)
Air handling unit
Inverter
RUN
RUN
Chapter6-12(P24˜25).p65
07.8.9, 12:52
Page 24
Adobe PageMaker 6.5J/PPC
Содержание FRENIC5000G11S Series
Страница 1: ......
Страница 2: ......
Страница 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Страница 166: ...4 12...
Страница 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Страница 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Страница 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Страница 235: ......
Страница 236: ......