34
7.7
VSD Object Configuration Properties (CPs)
This section details VSD object configuration properties (CPs) that need supplemental descriptions. For CPs not
found in this section, refer to Section 7.3 "VSD Object."
(1) SCPT_maxRcvTime
Receive heartbeat. This CP specifies the heartbeat receive interval for input NVs listed in Table 7-11 in
block. If no data is received within this interval after the reception of the last data, the interface card
interprets the state as a LONWORKS communications error.
Setting the heartbeat time at 0.0 s does not break the connection to the LONWORKS network even if no
data is received.
For details about the settings and activities on a LONWORKS connection break, refer to Chapter 8,
Section 8.1 "Specifying an Inverter Reaction to LONWORKS Communications Errors."
- Data setting range: 0.0 to 6553.4 s (0.1 s resolution)
- Default setting: 0.0 s (Ignore connection break)
Writing a value (e.g., 6553.5) exceeding the data setting range to this CP displays the value but
does not update the internal value, retaining the previously written data.
Table 7-11 NVs with Receive Heartbeat Time Specified by SCPT_maxRcvTime
Index
NV name
nv1 nviDrvSpeedStpt
nv2 nviDrvSpeedScale
nv8 nviOpeCmd
nv9 nviFreqCmd
nv13 nviAOCmd
nv14, nv15
nviDOcmd_Y1, Y2
nv16 nviFWDcmd
nv17 to nv21
nviXcmd_1 to 5
(2) SCPT_maxSendTime
Send heartbeat. This CP specifies the constant updating period for all output NVs listed in Table 7-12 below
in block. Specifying it periodically updates those NVs that include the internal monitor values.
Setting the send heartbeat at 0.0 s does not cause updating.
- Data setting range: 0.0 to 6553.4 s (0.1 s resolution)
- Default setting: 0.0 s (No periodic updating)
Table 7-12 NVs with Send Heartbeat Time Specified by SCPT_maxSendTime
Index
NV name
Index
NV name
nv3 nvoDrvCurnt
nv32 nvoDrvTemp_2
nv4 nvoDrvSpeed
nv33 nvoReadParamVal
nv5 nvoDrvVolt
nv35 nvoAiVal_1
nv6 nvoDrvPwr
nv36 nvoAiVal_2
nv23 nvoOpeStatus
nv37 nvoAiVal_3
nv24 nvoOutputFreq
nv38 nvoPIDFb
nv25
nvoDrvTorque
nv39 to nv43
nvoYstatus_1 to 5
nv26
nvoDrvEnergy
nv44 to nv48
nvoXstatus_1 to 5
nv31 nvoDrvTemp_1
Содержание LONWORKS OPC-LNW
Страница 3: ......
Страница 4: ......
Страница 9: ...5 4 10 LED P N DC 25V 4 1 1 2 2 2 CN1 4 2 4 1 4 1 CN1 4 1 4 2 3 5 4...
Страница 10: ...6 CN1 4 1 FRENIC HVAC A port 4 2 FRENIC HVAC A port 4 2 2 4 2...
Страница 13: ...9 5 3 LONWORKS LONWORKS FRENIC HVAC 7 5kW FRENIC HVAC 22kW 5 4...
Страница 41: ...ENGLISH English Version...
Страница 42: ......
Страница 81: ...MEMO...
Страница 82: ...MEMO...