nv35 nvoAIval_1
SNVT_lev_percent This output reports the input voltage at terminal
[12].
(100% at 10 V, 0% at 0 V)
M49 p.
27
nv36 nvoAIval_2
SNVT_lev_percent This output reports the input current at terminal
[C1].
(100% at 20 mA, 0% at 4 mA or 0 mA)
M50 p.
27
nv37 nvoAIval_3
SNVT_lev_percent This output reports the input voltage at terminal
[V2].
(100% at 10 V, 0% at 0 V)
M54 p.
27
nv38 nvoPIDFb
SNVT_lev_percent This output reports the PID feedback value
(%).
M72 p.
28
nv39 nvoYstatus_1
SNVT_switch
This output reports the status of digital output
terminal [Y1] whose function is assigned by
E20.
M15 p.
28
nv40 nvoYstatus_2
SNVT_switch
This output reports the status of digital output
terminal [Y2] whose function is assigned by
E21.
M15 p.
28
nv41 nvoYstatus_3
SNVT_switch
This output reports the status of digital output
terminal [Y3] whose function is assigned by
E22.
M15 p.
28
nv42 nvoYstatus_4
SNVT_switch
Reserved.
-
-
nv43 nvoYstatus_5
SNVT_switch
This output reports the status of digital output
terminal [Y5A/C] whose function is specified by
E24.
M15 p.
28
nv44 nvoXstatus_1
SNVT_switch
This output reports the status of a terminal
command assigned to digital input terminal
[X1].
When E01 data is "25" (Universal DI), this
output reports the ON/OFF state of the
physical terminal [X1].
M13 p.
28
nv45 nvoXstatus_2
SNVT_switch
This output reports the status of a terminal
command assigned to digital input terminal
[X2].
When E02 data is "25" (Universal DI), this
output reports the ON/OFF state of the
physical terminal [X2].
M13 p.
28
nv46 nvoXstatus_3
SNVT_switch
This output reports the status of a terminal
command assigned to digital input terminal
[X3].
When E03 data is "25" (Universal DI), this
output reports the ON/OFF state of the
physical terminal [X3].
M13 p.
28
nv47 nvoXstatus_4
SNVT_switch
This output reports the status of a terminal
command assigned to digital input terminal
[X4].
When E04 data is "25" (Universal DI), this
output reports the ON/OFF state of the
physical terminal [X4].
M13 p.
28
nv48 nvoXstatus_5
SNVT_switch
This output reports the status of a terminal
command assigned to digital input terminal
[X5].
When E05 data is "25" (Universal DI), this
output reports the ON/OFF state of the
physical terminal [X5].
M13 p.
28
nv49 nvoInAlarm
SNVT_switch
This output remains ON when the inverter is in
an alarm state or has not canceled the recent
alarm.
M14 -
nv50 nvoAlarm
UNVT_alarm_cod
(1 byte decimal)
This output reports the code of an alarm that is
occurring or has occurred most recently.
M16 p.
29
Содержание LONWORKS OPC-LNW
Страница 3: ......
Страница 4: ......
Страница 9: ...5 4 10 LED P N DC 25V 4 1 1 2 2 2 CN1 4 2 4 1 4 1 CN1 4 1 4 2 3 5 4...
Страница 10: ...6 CN1 4 1 FRENIC HVAC A port 4 2 FRENIC HVAC A port 4 2 2 4 2...
Страница 13: ...9 5 3 LONWORKS LONWORKS FRENIC HVAC 7 5kW FRENIC HVAC 22kW 5 4...
Страница 41: ...ENGLISH English Version...
Страница 42: ......
Страница 81: ...MEMO...
Страница 82: ...MEMO...