7.3.2 List of VSD object network variables (NVs)
Table 7-4 lists the summary of VSD object network variables (NVs). The function code column in the table
shows their associated inverter's function codes.
Some of the VSD object input and output NVs are detailed in Sections 7.4 and 7.5, respectively.
Table 7-4 VSD Object Network Variables
Index
Variable name
Variable type
Descriptions
Function
code Refer to:
nv1 nviDrvSpeedStpt
SNVT_switch
This input provides start/stop commands and a
low-resolution speed setpoint.
(as a percentage of SCPT_nomFreq)
- p.
22
nv2 nviDrvSpeedScale SNVT_lev_percent This input provides scaling for a low-resolution
speed setpoint. (Negative values indicate
reverse motor direction.)
- p.
22
nv3 nvoDrvCurnt
SNVT_amp
This output reports the output current (RMS)
with 0.1 A resolution.
M11 -
nv4 nvoDrvSpeed
SNVT_lev_percent This output reports the output speed.
(as a percentage of SCPT_nomFreq)
- p.
26
nv5 nvoDrvVolt
SNVT_volt
This output reports the output voltage (RMS)
with 0.1 V resolution.
M12 -
nv6 nvoDrvPwr
SNVT_power_kilo
This output reports the output power with 0.1
kW resolution.
M10 -
nv7 nvoDrvRunHours
SNVT_time_hour This output reports the cumulative motor run
time.
(Diagnostic reference of the mechanical
component service life)
Z40 -
nv8 nviOpeCmd
SNVT_state
This input provides run commands including
run forward command, run reverse command,
and terminal commands assigned to
general-purpose, digital input terminals.
Functionally equivalent to function code S06
(dedicated to inverter communication).
S06 p.
23
nv9 nviFreqCmd
SNVT_freq_hz
This input provides frequency command with
0.1 Hz resolution.
S05 p.
23
nv10 nviReadParamCode SNVT_count
This input specifies a target inverter's function
code to read out its data to nv33
nvoReadParamVal.
-
pp. 23
and 31
nv11 nviWriteParaCode
SNVT_count
This input specifies a target inverter's function
code to write data with nv12 nviWriteParamVal.
-
pp. 24
and 32
nv12 nviWriteParamVal
SNVT_count
This input contains data to write into the
inverter's function code specified by nv11
nviWriteParaCode.
The write result is output to nv34.
-
pp. 24
and 32
nv13 nviAOcmd
SNVT_lev_percent This input specifies any output level for the
inverter's analog output terminal.
Functionally equivalent to function code S12
(dedicated to inverter communication).
S12
pp. 24
and 10
nv14 nviDOcmd_Y1
SNVT_switch
This input turns the inverter's digital output
terminal [Y1] ON/OFF.
If the value is "1," [Y1] is ON. (Setting E20 to
"27" (Universal DO) is needed.)
S07
pp. 24
and 10
nv15 nviDOcmd_Y2
SNVT_switch
This input turns the inverter's digital output
terminal [Y2] ON/OFF.
If the value is "1," [Y2] is ON. (Setting E21 to
"27" (Universal DO) is needed.)
S07
pp. 24
and 10
nv16 nviFWDcmd
SNVT_switch
This input turns terminal command
FWD
(bit
XF of S06) ON/OFF, which is assigned to the
inverter's digital input terminal [FWD] with
function code E98.
FWD
runs a motor forward by factory default.
S06
pp. 25
and 10
Содержание LONWORKS OPC-LNW
Страница 3: ......
Страница 4: ......
Страница 9: ...5 4 10 LED P N DC 25V 4 1 1 2 2 2 CN1 4 2 4 1 4 1 CN1 4 1 4 2 3 5 4...
Страница 10: ...6 CN1 4 1 FRENIC HVAC A port 4 2 FRENIC HVAC A port 4 2 2 4 2...
Страница 13: ...9 5 3 LONWORKS LONWORKS FRENIC HVAC 7 5kW FRENIC HVAC 22kW 5 4...
Страница 41: ...ENGLISH English Version...
Страница 42: ......
Страница 81: ...MEMO...
Страница 82: ...MEMO...