16
Index
Variable name
Variable type
Descriptions
Function
code Refer to:
nv17 nviXcmd_1
SNVT_switch
This input turns a terminal command (bit X1 of
S06) ON/OFF, which is assigned to the
inverter's digital input terminal [X1] with
function code E01.
S06
pp. 25
and 10
nv18 nviXcmd_2
SNVT_switch
This input turns a terminal command (bit X2 of
S06) ON/OFF, which is assigned to the
inverter's digital input terminal [X2] with
function code E02.
S06
pp. 25
and 10
nv19 nviXcmd_3
SNVT_switch
This input turns a terminal command (bit X3 of
S06) ON/OFF, which is assigned to the
inverter's digital input terminal [X3] with
function code E03.
S06
pp. 25
and 10
nv20 nviXcmd_4
SNVT_switch
This input turns a terminal command (bit X4 of
S06) ON/OFF, which is assigned to the
inverter's digital input terminal [X4] with
function code E04.
S06
pp. 25
and 10
nv21 nviXcmd_5
SNVT_switch
This input turns a terminal command (bit X5 of
S06) ON/OFF, which is assigned to the
inverter's digital input terminal [X5] with
function code E05.
S06
pp. 25
and 10
nv22 nviAlarmReset
SNVT_switch
Turning this variable ON (TRUE) clears alarm
in the inverter.
Once it turns ON, it automatically returns to
OFF (False).
S14 p.
25
nv23 nvoDrvStatus
SNVT_state
This output reports the running status.
Functionally equivalent to function code M14
(dedicated to inverter communication).
M14 p.
26
nv24 nvoOutputFreq
SNVT_freq_hz
This output reports the output frequency with
0.1 Hz resolution.
M09 -
nv25 nvoDrvTorque
SNVT_lev_percent This output reports the output torque as a
percentage of the rated torque with 0.005%
resolution.
M07 -
nv26 nvoDrvEnergy
SNVT_elec
_kwh This output reports the inverter's cumulative
power consumption in watt-hours.
W81 -
nv27 nvoDrvOpeHours
SNVT_time_hour This output reports the cumulative inverter run
time.
(Diagnostic reference data for inverter lifetime)
W70 -
nv28 nvoOpeTm_1
SNVT_time_hour This output reports the cumulative run time of
electrolytic capacitors on printed circuit boards.
(Diagnostic reference data for service lifetime
of the control circuit)
W67 -
nv29 nvoOpeTm_2
SNVT_time_hour This output reports the cumulative run time of
the cooling fan.
W68 -
nv30 nvoDCbusCapacity SNVT_lev_percent This output reports the current capacitance of
the DC link bus capacitor in %, based on the
capacitance when shipped as 100%.
W75 -
nv31 nvoDrvTemp_1
SNVT_temp
This output reports the inverter internal
temperature with 1
°
C resolution.
M61 -
nv32 nvoDrvTemp_2
SNVT_temp
This output reports the heat sink temperature
with 1
°
C resolution.
M62 -
nv33 nvoReadParamVal
SNVT_count
This outputs function code data read. For the
format, refer to Section 7.6.
-
pp. 26
and 31
nv34 nvoAccessErrCode UNVT_ErrCode
(1byteHex x 3)
This outputs the error code and accessed
function code after completion of writing to
inverter's function code.
It updates only when accessed to nv11 and
nv12 and outputs to LON.
-
pp. 27
and 32
Содержание LONWORKS OPC-LNW
Страница 3: ......
Страница 4: ......
Страница 9: ...5 4 10 LED P N DC 25V 4 1 1 2 2 2 CN1 4 2 4 1 4 1 CN1 4 1 4 2 3 5 4...
Страница 10: ...6 CN1 4 1 FRENIC HVAC A port 4 2 FRENIC HVAC A port 4 2 2 4 2...
Страница 13: ...9 5 3 LONWORKS LONWORKS FRENIC HVAC 7 5kW FRENIC HVAC 22kW 5 4...
Страница 41: ...ENGLISH English Version...
Страница 42: ......
Страница 81: ...MEMO...
Страница 82: ...MEMO...