31
ENGLISH
081E (hexadecimal) = 2078 (decimal)
7.6
Reading and Writing from/to Inverter's Function Codes
7.6.1 Reading from inverter's function codes
Use nv10 nviReadParamCode and nv33 nvoReadParamVal. This section summarizes the reading procedure.
(1) Enter the inverter's target function code into nv10 nviReadParamCode in the 16-bit format shown below.
This starts the readout process of the inverter's function code.
(Example) Reading H30 from the inverter
H: Function code group 08
30:
1E
(hexadecimal)
bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9
bit 8
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2 bit 1 bit 0
Inverter's function code group
Function code number
Inverter's function code group: Group of function codes (F, E, C etc.). See Table 7-9 below.
Function code number:
2-digit number following the function code group. For example, 98 in E98.
(2) nv33 nvoReadParamVal outputs the data of the function code specified by nv10 nviReadParamCode, then
the readout process terminates. The value is subject to the format of individual function codes.
For details about the data format of individual function codes, refer to the RS-485 Communication
User's Manual (MEH448), Chapter 5, Section 5.2 "Data Formats."
Input of a non-existing function code returns "0" to nv33 nvoReadParamVal.
If a running readout process for a function code is interrupted by another readout request, the
interrupting request will be ignored. This interface card does not support any output NV that
identifies whether a readout process is already running. To run the read process very frequently,
therefore, it is recommended that the software be so designed that it monitors the input/output
status of nv10 nviReadParamCode and nv33 nvoReadParamVal, confirms the completion of all
the previous processes, and then starts a new readout process.
Table 7-9 Function Code Groups
Classifi-
cation
Group
number
Function code name
Classifi-
cation
Group
number
Function code name
S
2
02h
Command Data
W1
23
17h
Monitor 3
M
3
03h
Monitor Data
W2
24
18h
Monitor 4
F
4
04h
Fundamental Functions
W3
25
19h
Monitor 5
E
5
05h
Extension Terminal Functions
X1
26
1Ah
Alarm 3
C
6 06h Control
Functions
X2
27
1Bh Alarm
4
P
7
07h
Motor 1 Parameters
Z1
28
1Ch
Alarm 5
H
8
08h
High Performance Functions
K
29
1Dh
Keypad Panel Function
A
9
09h
Motor 2 Parameters
T
30
1Eh
Clock Timer Function
o
10
0Ah
Optional Functions
E1
31
1Fh
Extension Terminal Functions 1
L
11
0Bh
For elevators
H1
32
20h
High Performance Function 1
r
12
0Ch
Motor 4 Parameters
o1
33
21h
Optional Functions 1
U
13
0Dh
Soft relay 1
U1
34
22h
Soft relay 2
J
14
0Eh
Application Function 1
M1
35
23h
Monitor Data 1
y 15
0Fh
Link
Functions
J1 36
24h
Application
Function
W
16
10h
Monitor Data 2
J2
37
25h
Application Function
X
17
11h
Alarm Data 1
J3
38
26h
Application Function
Z
18
12h
Alarm Data 2
J4
39
27h
Application Function
b 19
13h
Motor
3
Parameters
J5 40
28h
Application
Function
d
20
14h
Application Functions 2
J6
41
29h
Application Function
d1
42
24Ah
Application
Function
Содержание LONWORKS OPC-LNW
Страница 3: ......
Страница 4: ......
Страница 9: ...5 4 10 LED P N DC 25V 4 1 1 2 2 2 CN1 4 2 4 1 4 1 CN1 4 1 4 2 3 5 4...
Страница 10: ...6 CN1 4 1 FRENIC HVAC A port 4 2 FRENIC HVAC A port 4 2 2 4 2...
Страница 13: ...9 5 3 LONWORKS LONWORKS FRENIC HVAC 7 5kW FRENIC HVAC 22kW 5 4...
Страница 41: ...ENGLISH English Version...
Страница 42: ......
Страница 81: ...MEMO...
Страница 82: ...MEMO...