7.3.3 List of VSD object configuration properties (CPs)
Table 7-5 lists the summary of VSD object configuration properties (CPs). The function code column in the
table shows their associated inverter's function codes. Modifying function code data can change the
associated CP value.
Some of these CPs have detailed descriptions in Section 7.7 (see the page given in the table below).
Refer to the user's manual of an inverter, "FUNCTION CODES" for supplementary information on the CPs.
Table 7-5 VSD Object CPs
CP name
Unit
Description
Default
Function
code
Refer
to:
SCPT_maxSetpoint 0.005%
Defines the maximum frequency as a percentage of
SCPT_nomFreq.
100.000
%
(60 Hz)
F03 -
SCPT_minSetpoint 0.005%
Defines the lower limit of the output frequency as a
percentage of SCPT_nomFreq.
0.000% F16
-
SCPT_maxSendTime
0.1 s
Sets the heartbeat send interval.
The concerned NV continues transmitting data at
this time intervals, regardless the data changing.
Specifying 0.0 s disables this CP.
0.0 s
-
p. 33
SCPT_nomRPM 1
r/min
Used to enter the nominal speed, 100% of the
percent speed command, in r/min.
Modifying this CP automatically replaces the value
of SCPT_nomFreq.
1800
r/min
- -
SCPT_nomFreq 0.1
Hz
Used to enter the nominal frequency, 100% of the
percent speed command, in Hz.
All percent speed commands refer to this value.
60.0 Hz -
p. 22
SCPT_rampUpTm 0.1
s Used to enter the ramp-up time from the zero to
maximum speed.
20.0 s
F07
-
SCPT_rampDownTm 0.1
s
Used to enter the ramp-down time from the
maximum to zero speed.
20.0 s
F08
-
(UCPT_rampUpTm2) -
Reserved.
-
-
-
(UCPT_rampDown
Tm2)
- Reserved.
- - -
SCPT_defScale
0.005%
Contains the default value for nviDrvSpeedScale.
100.000
%
- -
SCPT_maxRcvTime
0.1 s
Sets the heartbeat receive interval.
If the concerned NV receives no data within this
interval, it interprets the transmission as being
broken.
Specifying 0.0 s disables this CP.
0.0 s
p.
33
SCPT_minDeltaLevel 0.5% Sets the minimum data change rate for an output
NV to start data transmission.
If the data change rate exceeds this value, the
concerned NV interprets the data as being
changed, starting data transmission.
Specifying 0.0% disables this CP.
0.0%
p.
34
SCPT_minSendTime 0.1
s Sets the minimum pause time for an output NV to
start data transmission.
Once the concerned NV finishes data transmission,
it does not start data transmission until this time has
elapsed even if the data change rate exceeds
SCPT_minDeltaLevel.
Setting 0.0 s disables this CP.
0.5 s
p. 34
UCPT_BaseFreq
0.1 Hz
Sets the base frequency of the inverter for motor 1.
50.0 Hz F04
-
(UCPT_JogFreq) - Reserved.
- - -
Содержание LONWORKS OPC-LNW
Страница 3: ......
Страница 4: ......
Страница 9: ...5 4 10 LED P N DC 25V 4 1 1 2 2 2 CN1 4 2 4 1 4 1 CN1 4 1 4 2 3 5 4...
Страница 10: ...6 CN1 4 1 FRENIC HVAC A port 4 2 FRENIC HVAC A port 4 2 2 4 2...
Страница 13: ...9 5 3 LONWORKS LONWORKS FRENIC HVAC 7 5kW FRENIC HVAC 22kW 5 4...
Страница 41: ...ENGLISH English Version...
Страница 42: ......
Страница 81: ...MEMO...
Страница 82: ...MEMO...