20
CP name
Unit
Description
Default
Function
code
Refer
to:
UCPT_JumpFreq
0.1 Hz x 4 Contains an ensemble of four inverter's function
codes specified in the array order shown below.
"Jump frequency 1, 2, 3 and jump frequency band"
0.0 Hz,
0.0 Hz,
0.0 Hz,
3.0 Hz
C01,
C02,
C03,
C04
-
UCPT_LinkFunc 1 Switches run and speed commands between
"enable" and "disable" via the LONWORKS
network.
Functionally equivalent to function code y98.
Setting y98 data to "3" enables run and speed
commands.
0
y98 p.
10
UCPT_multStepFreq1 0.01
Hz Sets the frequency to be applied when multistep
frequency 1 is selected.
Multistep frequency: Assigning terminal commands
to digital input terminals [X1] to [X5] and [FWD] with
E01 to E05 and E98 and turning those terminals
ON/OFF can select the multistep frequency.
0.00 Hz
C05
-
UCPT_PIDsettings
0.001,
0.1 s,
0.01 s,
0.1 s
Contains an ensemble of four PID parameters
specified in the array order shown below.
"P gain, I time, D time and feedback filter time
constant"
0.100,
0.0 s,
0.00 s,
0.5 s
J03,
J04,
J05,
J06 *
1
-
UCPT_StartFreq
0.1 Hz
Sets the starting frequency.
0.5 Hz
F23
-
UCPT_StopFreq
0.1 Hz
Sets the stop frequency.
0.2 Hz
F25
-
(UCPT_TorqLimit) -
Reserved.
- - -
UCPT_CblLossMode 1
Specifies an action to follow when a
communications line break error occurs on the
LONWORKS network.
Functionally equivalent to function code o27.
0 o27
p.
35
UCPT_CblLossTimer 0.1
s Sets the timer to determine the issuing timing of
er5
alarm triggered by a communications line
break on the LONWORKS network.
Functionally equivalent to function code o28.
0.0 s
o28
p. 35
UCPT_FlyingStart
Mode
1
Specifies the auto search for idling motor's speed.
In the auto search mode, the frequency can be
specified by function code H17.
0
(Disable)
H09 -
UCPT_momentary
Pwr
LossMode
1
Specifies the restart mode after a momentary power
failure.
Functionally equivalent to function code F14.
1 F14
-
UCPT_AutoRestart 1
Specifies the number of auto-resetting times for
automatically escaping the tripped state.
Functionally equivalent to function code H04.
H05 specifies the reset interval.
0 H04
-
UCPT_SendDelay
AfterDevRdy
0.1 s
Specifies the data transmission start delay time for
the LONWORKS interface card.
The output NV starts data transmission after this
delay time has elapsed from when the interface
card is powered up or receives a reset command
from the LONWORKS integration tool.
This CP should be used to strictly manage the
starting time of data transmission on the whole
network.
Specifying 0.0 s makes the NV start data
transmission upon completion of initialization of the
card. *
2
0.0 s
―
-
*
1
These function codes differ depending on the target inverter. For details about the PID control of the
inverter, refer to the "J codes" and "PID Control Block" given in the Inverter User's Manual.
Содержание LONWORKS OPC-LNW
Страница 3: ......
Страница 4: ......
Страница 9: ...5 4 10 LED P N DC 25V 4 1 1 2 2 2 CN1 4 2 4 1 4 1 CN1 4 1 4 2 3 5 4...
Страница 10: ...6 CN1 4 1 FRENIC HVAC A port 4 2 FRENIC HVAC A port 4 2 2 4 2...
Страница 13: ...9 5 3 LONWORKS LONWORKS FRENIC HVAC 7 5kW FRENIC HVAC 22kW 5 4...
Страница 41: ...ENGLISH English Version...
Страница 42: ......
Страница 81: ...MEMO...
Страница 82: ...MEMO...