29
ENGLISH
Depending on the command assignment to inverter's digital input terminals, some ON/OFF
commands via the LONWORKS network using these NVs may be ignored. On the other hand,
some commands entered from the terminal block may be unconditionally validated. For details
about these events, refer to the RS-485 Communication User's Manual (MEH448), Chapter 5,
Section 5.1.2 [3] "Operation command data."
(9) nv50 nvoAlarm
This NV outputs the contents of an alarm that is occurring or has recently occurred.
- Variable type:
UNVT_alarm_cod (1 byte, decimal)
- Data setting range: 0 to 255
- CPs for control of the affected network bandwidth: SCPT_minSendTime
- Output timing: At the time of data change or after the time specified by SCPT_minSendTime (if
specified)
Table 7-8 Alarm Code Table
Alarm codes
in
M16 to M19
Description
Alarm codes
in
M16 to M19
Description
0 (00
H
) No
alarm
---
23 (17
H
)
Overload of motor 1
0l1
1 (01
H
) Overcurrent
(during acceleration)
0c1
24 (18
H
)
Overload of motor 2
0l2
2 (02
H
) Overcurrent
(during deceleration)
0c2
44 (2C
H
)
Overload of motor 3
0l3
3 (03
H
) Overcurrent
(During running at constant
speed)
0c3
45 (2D
H
)
Overload of motor 4
0l4
5 (05
H
) Grounding
fault
ef
25 (19
H
) Inverter
overload
0lu
6 (06
H
) Overvoltage
(during acceleration)
0u1
27 (1B
H
) Over
speed
error
0s
7 (07
H
) Overvoltage
(during deceleration)
0u2
28 (1C
H
)
Wiring break in a PG
pg
8 (08
H
) Overvoltage
(during running at constant speed
or stopped)
0u3
29 (1D
H
)
Wiring break in a NTC
thermistor
nrb
10 (0A
H
) Undervoltage
lu
31 (1F
H
) Memory
error
er1
11 (0B
H
)
Input phase loss
lIn
32 (20
H
)
Keypad communications error
er2
12 (0C
H
)
Power supply frequency error
fre
33 (21
H
) CPU
error
er3
13 (0D
H
)
AC fuse blown
acf
34 (22
H
)
Option communications error
er4
14 (0E
H
) Fuse
blown
fus
35 (23
H
) Option
error
er5
15 (0F
H
)
DC fuse blown
dcf
36 (24
H
) Operation
protection
er6
16 (10
H
) Charger
circuit
fault
pbf
37 (25
H
) Tuning
error
er7
17 (11
H
) Heat
sink
overheat
0h1
18 (12
H
) External
alarm
0h2
38 (26
H
)
53 (35
H
)
RS-485 communications error
(COM port 1)
(COM port 2)
er8
erp
19 (13
H
) Inverter
internal
overheat
0h3
39 (27
H
)
A/D converter defection
er9
20 (14
H
) Motor
protection
(PTC/NTC thermistor)
0h4
42 (29
H
)
Out-of-step detection
erd
22 (16
H
) Braking
resistor
overheat
dbh
46 (2E
H
) Output
phase
loss
0pl
Содержание LONWORKS OPC-LNW
Страница 3: ......
Страница 4: ......
Страница 9: ...5 4 10 LED P N DC 25V 4 1 1 2 2 2 CN1 4 2 4 1 4 1 CN1 4 1 4 2 3 5 4...
Страница 10: ...6 CN1 4 1 FRENIC HVAC A port 4 2 FRENIC HVAC A port 4 2 2 4 2...
Страница 13: ...9 5 3 LONWORKS LONWORKS FRENIC HVAC 7 5kW FRENIC HVAC 22kW 5 4...
Страница 41: ...ENGLISH English Version...
Страница 42: ......
Страница 81: ...MEMO...
Страница 82: ...MEMO...